F0018 THERM FAIL fault in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/F0018 THERM FAIL fault in ABB ACS310 drive

The F0018 THERM FAIL fault on the ABB ACS310 drive indicates an internal hardware failure where the thermistor sensor used to measure internal power semiconductor heatsink temperature is open or short-circuited. The drive locks out operation to prevent unmonitored thermal destruction of the power stage.

The ACS310 power module incorporates an internal Negative Temperature Coefficient (NTC) thermistor directly on the power semiconductor heatsink. The drive microcontroller converts thermistor resistance into an internal temperature reading for thermal modeling. If the circuit detects an open-circuit (infinite resistance) or dead short (zero resistance), the safety architecture cannot verify inverter thermal safety. To prevent catastrophic thermal runaway of the IGBT modules, the drive immediately terminates PWM gate pulses and blocks further inverter operation.

What Causes F0018 in ABB ACS310?

  1. Broken, cracked, or open-circuit internal NTC thermistor element mounted on the heatsink substrate.
  2. Cracked solder joints, trace fracture, or ribbon cable disconnect on the internal power board assembly.
  3. Internal sensor short circuit caused by conductive metallic dust, condensation, or severe chemical contamination.
  4. Failure of the analog-to-digital converter (ADC) channel or sensing circuitry on the main control board.
  5. Severe physical shock or extreme thermal cycling causing mechanical separation of internal components.

Step-by-Step Troubleshooting and Solutions

  1. Disconnect incoming AC line power from terminals L1, L2, L3, wait for the DC bus capacitors to fully discharge, and inspect the drive for physical contamination.
  2. Verify ambient operating temperatures around the drive; ensure the unit has not been exposed to extreme sub-zero conditions below -10 °C that distort resistance curves.
  3. Inspect internal cooling air passages and clear conductive metallic particles or dust using clean, dry compressed air.
  4. Reapply power and attempt a control reset to determine whether the ADC measurement initializes properly upon reboot.
  5. Because F0018 represents an unrecoverable internal hardware fault, if the trip persists after power cycling, contact an authorized ABB service center for drive repair or replacement.

Preventative Maintenance to Avoid F0018 Faults

Install drives within clean, dry, climate-controlled electrical enclosures (IP20/IP54). Ensure panel cooling fans and air intake filters are cleaned regularly to prevent conductive airborne dust, moisture, and extreme thermal cycling from damaging internal surface-mount components.

Frequently Asked Questions (FAQs)

What is the meaning of F0018 fault in ABB ACS310 drive?

It indicates that the internal thermistor used to monitor drive heatsink temperature is open or short-circuited, representing an internal hardware failure.

What are the primary causes of F0018 fault?

The primary causes are a broken or shorted internal NTC thermistor, damaged internal printed circuit board traces, conductive metallic dust ingress, or ADC sensing failure.

How do I troubleshoot and correct F0018 fault?

Verify ambient operating temperatures, inspect the drive for internal moisture or dust contamination, cycle main power, and send the drive for authorized repair if the fault remains.