F1004 fault in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/F1004 fault in ABB ACS310 drive

The F1004 fault on the ABB ACS310 indicates an invalid analog output scaling conflict where the configured minimum scale value is greater than or equal to the maximum scale value. The drive halts start commands and trips to prevent sending misleading telemetry to external monitoring equipment.

The ACS310 digital signal processor maps internal actual signals (such as motor frequency, output current, or process feedback) to terminal AO via an internal digital-to-analog converter (DAC). The DAC transfer function uses mathematical slope scaling based on parameter group 15 ANALOG OUTPUTS. If parameter 1504 MINIMUM AO1 is programmed to a value greater than or equal to parameter 1505 MAXIMUM AO1, a division-by-zero or negative scaling slope occurs. To prevent distorted signal transmission that could corrupt supervisory PLC logging or external PID loops, the drive firmware inhibits motor modulation and asserts fault F1004.

What Causes F1004 in ABB ACS310?

  1. Parameter 1504 MINIMUM AO1 programmed with a numerical value higher than parameter 1505 MAXIMUM AO1.
  2. Both parameters 1504 and 1505 entered with identical numerical values during keypad commissioning.
  3. Uploading a corrupted custom parameter file or unverified backup set into drive memory.
  4. Attempting to create an inverted analog output response by reversing minimum and maximum scale points.
  5. Selecting a signal in parameter 1501 AO1 CONTENT SEL that conflicts with existing boundary thresholds.

Step-by-Step Troubleshooting and Solutions

  1. Navigate to parameter group 15 ANALOG OUTPUTS using the Basic or Assistant Control Panel.
  2. Check the values stored in parameter 1504 MINIMUM AO1 and parameter 1505 MAXIMUM AO1.
  3. Ensure that the condition 1504 MINIMUM AO1 < 1505 MAXIMUM AO1 strictly applies (e.g., set minimum to 0.0 mA and maximum to 20.0 mA).
  4. If an inverted output signal is needed, utilize dedicated inversion settings rather than entering a minimum scale larger than the maximum.
  5. Measure the output current across terminal AO and analog ground AGND using a multimeter to verify correct signal tracking.

Preventative Maintenance to Avoid F1004 Faults

Document all analog output scaling standards in drive commissioning logs, verify parameter group 15 values after performing firmware upgrades or parameter cloning, and validate analog loop telemetry before placing equipment into service.

Frequently Asked Questions (FAQs)

What is the meaning of F1004 fault in ABB ACS310 drive?

The F1004 fault indicates that the analog output scaling parameters are invalid because the minimum scale setting is not lower than the maximum scale.

What are the primary causes of F1004 fault?

It is caused by setting parameter 1504 equal to or higher than parameter 1505 during manual programming or backup restores.

How do I troubleshoot and correct F1004 fault?

Access parameter group 15 on the keypad and ensure parameter 1504 MINIMUM AO1 is strictly set less than parameter 1505 MAXIMUM AO1.