The F1006 fault on the ABB ACS310 indicates an extension relay output parameter conflict where external relay functions are programmed without an active MREL-01 module detected. The drive blocks operation to prevent unmonitored relay switching sequences.
The standard ACS310 chassis comes equipped with a single onboard form-C relay output (RO1). To control auxiliary pumps or system indications, an optional MREL-01 relay output extension module must be installed, providing three additional relays (RO2, RO3, and RO4). If parameters 1402 RELAY OUTPUT 2, 1403 RELAY OUTPUT 3, or 1410 RELAY OUTPUT 4 are configured with active non-zero functions while the MREL-01 module is absent, unseated, or damaged, the internal microprocessor cannot address the peripheral hardware registers. The drive triggers fault F1006 to prevent unexecuted relay logic from causing equipment failure.
What Causes F1006 in ABB ACS310?
- Relay extension parameters
1402,1403, or1410configured with non-zero values while no MREL-01 module is installed. - Mechanical unseating or bent, oxidized connector pins between the MREL-01 module and the drive control board.
- Uploading a parameter file from an MREL-equipped drive to a standard drive lacking the extension module.
- Failure of the auxiliary power supply rail feeding the peripheral relay extension board.
- Defective hardware or damaged relay coils on the MREL-01 module circuit card.
Step-by-Step Troubleshooting and Solutions
- Verify whether the physical MREL-01 relay extension module is securely mounted in the drive option slot.
- If no MREL module is installed, set parameters
1402 RELAY OUTPUT 2,1403 RELAY OUTPUT 3, and1410 RELAY OUTPUT 4to0 (NOT SEL). - De-energize the drive, remove the MREL-01 module, check for bent or dirty header pins, and re-seat it firmly.
- Confirm that the module firmware handshake is acknowledged by checking option card diagnostic parameters.
- Test continuity and auxiliary voltage on relay output terminals
RO2,RO3, andRO4after clearing the fault.
Preventative Maintenance to Avoid F1006 Faults
Fasten option module retaining screws securely to prevent vibration-induced pin disconnection, inspect module connectors during regular cabinet audits, and verify hardware compatibility before transferring parameter sets.
Frequently Asked Questions (FAQs)
What is the meaning of F1006 fault in ABB ACS310 drive?
The F1006 fault indicates that extension relay outputs are configured in software but the required MREL-01 hardware module is missing or disconnected.
What are the primary causes of F1006 fault?
It is caused by setting parameters 1402, 1403, or 1410 to active values without a properly seated MREL-01 extension module.
How do I troubleshoot and correct F1006 fault?
Install and securely seat the MREL-01 module, or set parameters 1402, 1403, and 1410 to NOT SEL if no extension module is used.