A2018 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2018 alarm in ABB ACS355 drive

The A2018 alarm indicates that the internal process PID controller in the ABB ACS355 drive has placed the unit into sleeping mode. This normal status alarm informs operators that demand is met and motor output has stopped to conserve energy.

During the sleep mode sequence, the drive ramps motor output to zero and deactivates inverter IGBT gate pulses, leaving the DC intermediate circuit charged and monitoring active transducer feedback. Sleep mode prevents continuous pump churning against deadhead valves, reducing mechanical wear and mechanical seal heating while awaiting wake-up threshold conditions on analog control loops.

What Causes A2018 in ABB ACS355?

  1. Process feedback variable exceeding the setpoint during low consumer demand periods.
  2. Motor running below sleep speed threshold configured in parameter 4023 PID SLEEP LEVEL.
  3. PID sleep delay timer expiring in parameter 4024 PID SLEEP DELAY.
  4. Closed discharge valves or low system draw in booster pump and fan ventilation systems.
  5. Miscalibrated pressure transducer delivering false high feedback to analog input terminal AI1.

Step-by-Step Troubleshooting and Solutions

  1. Verify process demand by checking pressure, flow, or temperature transmitters against parameter 0130 PID1 FBK VALUE.
  2. Inspect sleep activation parameter 4022 SLEEP SELECTION and verify wake-up deviation in parameter 4025 WAKE-UP DEV.
  3. Adjust sleep frequency in parameter 4023 PID SLEEP LEVEL to prevent premature shutoffs during moderate process draw.
  4. Confirm that the wake-up delay time in parameter 4026 WAKE-UP DELAY is tuned to avoid short cycling under fluctuating system pressures.
  5. Test feedback sensor wiring on terminal block X1A (terminals +24V, AI1, GND) for intermittent electrical noise or drift.

Preventative Maintenance to Avoid A2018 Faults

Calibrate pressure transmitters annually, inspect check valves for backflow leakage that causes rapid wake-sleep cycling, and fine-tune sleep delays to match seasonal process demands.

Frequently Asked Questions (FAQs)

What is the meaning of A2018 fault in ABB ACS355 drive?

The A2018 alarm is an operational notification indicating that process conditions have met sleep criteria, temporarily stopping motor rotation.

What are the primary causes of A2018 fault?

Common causes include low process fluid consumption, satisfying pressure setpoints, or reaching programmed sleep frequencies.

How do I troubleshoot and correct A2018 fault?

Review process demand sensors, verify sleep level settings in parameter 4023, and adjust wake-up thresholds in parameter 4025.