A2021 START ENABLE 1 MISSING alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2021 START ENABLE 1 MISSING alarm in ABB ACS355 drive

The A2021 alarm indicates that the ABB ACS355 drive has received a run command while the mandatory Start Enable 1 interlock signal is inactive. The drive enters an inhibit state, preventing inverter modulation and holding the motor at zero speed until the safety circuit is completed.

When Start Enable 1 is configured in the firmware, the digital control board monitors assigned digital inputs (such as DI1 through DI5) or fieldbus control words before releasing firing pulses to the IGBT gate drivers. If this digital permit circuit opens, the intermediate DC bus remains charged, but modulation stops instantly. This protective mechanism ensures downstream machinery or safety gates are firmly closed before shaft rotation can occur, protecting equipment from accidental starts.

What Causes A2021 in ABB ACS355?

  1. The digital input configured under parameter 1608 (START ENABLE 1) is physically disconnected, loose, or broken.
  2. An external safety interlock, guard limit switch, or emergency gate relay wired in series with the start enable line has opened.
  3. Parameter 1608 is improperly configured to an unused input terminal or set to an active fieldbus communication bit.
  4. The +24V DC auxiliary control voltage loop (terminal +24V or DCOM) has lost continuity or experienced a power supply sag.
  5. Fieldbus communication timeout or bad bit configuration in parameter group 53 (EFB PROTOCOL) preventing bit assertion.

Step-by-Step Troubleshooting and Solutions

  1. Check parameter 1608 (START ENABLE 1) via the control panel to identify the assigned input terminal (e.g., DI1 to DI5 or COMM).
  2. Measure DC voltage between the assigned digital input terminal and DCOM using a multimeter; verify a clean +24V DC signal is present.
  3. Inspect external interlock switches, safety gate contacts, and emergency pull-cords wired to the enable circuit for mechanical trip conditions.
  4. If controlling via Modbus or fieldbus adapter, check parameter group 51/53 and ensure control word bit 3 or mapped enable bit is high.
  5. Review digital input status directly in parameter 0118 (DI 5-1 STATUS) to isolate whether the issue is hardware wiring or parameterization.

Preventative Maintenance to Avoid A2021 Faults

Periodically torque all control wiring terminals on terminal strip X1 to ensure vibration does not cause intermittent contact loss. Inspect external safety relay contacts for pitting or oxidation, and implement noise-shielded control cables with single-point grounding to prevent inductive interference from triggering false interlock dropouts.

Frequently Asked Questions (FAQs)

What is the meaning of A2021 fault in ABB ACS355 drive?

The A2021 alarm indicates that the drive has received a run command but cannot start because its designated Start Enable 1 interlock circuit is open.

What are the primary causes of A2021 fault?

Common causes include open physical safety gates, loose digital input wiring, missing 24V DC control power, or misconfigured settings in parameter 1608.

How do I troubleshoot and correct A2021 fault?

Verify parameter 1608 assignment, measure 24V DC at the assigned digital input terminal, and inspect upstream safety interlocks for open contacts.