A5015 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A5015 alarm in ABB ACS355 drive

The A5015 alarm warns that local keypad control mode has been disabled because an active software lock is enforced. The drive prevents operators from switching between remote and local operation to protect automated control commands.

When the local lockout feature is enabled, the drive firmware enforces supervisory isolation over motor control commands. Motor modulation continues uninterrupted under fieldbus or terminal block commands, but the control panel micro-controller rejects manual LOC/REM toggle requests, preventing operators from overriding PLC automation sequences or interrupting synchronized industrial processes.

What Causes A5015 in ABB ACS355?

  1. Parameter 1606 LOCAL LOCK is set to 1 (TRUE), permanently disabling local control mode.
  2. A digital input designated in parameter 1606 LOCAL LOCK is energized, actively enforcing local lockout.
  3. Supervisory PLC or SCADA system writing a local disable command over an RS485 Modbus interface.
  4. Unauthorized operator attempting to manually halt a drive assigned exclusively to remote fieldbus control.
  5. Corrupted user parameter set or macro configuration in parameter Group 16 SYSTEM CONTROLS.

Step-by-Step Troubleshooting and Solutions

  1. Navigate to parameter Group 16 and inspect parameter 1606 LOCAL LOCK to identify the current lock state.
  2. Change parameter 1606 LOCAL LOCK to 0 (FALSE) to restore full keypad access.
  3. If parameter 1606 LOCAL LOCK is mapped to an input such as DI3, check terminal block X1A with a DC voltmeter.
  4. Verify serial fieldbus commands in parameter Group 53 EFB PROTOCOL to ensure remote networks are not locking the panel.
  5. Confirm drive parameter access security settings in parameter 1602 PARAMETER LOCK to permit configuration writes.

Preventative Maintenance to Avoid A5015 Faults

Maintain accurate control architecture documentation indicating which machines utilize local locks, and train operators to avoid forcing manual mode transitions on automated equipment lines.

Frequently Asked Questions (FAQs)

What is the meaning of A5015 fault in ABB ACS355 drive?

The A5015 alarm indicates that local keypad control is inhibited because the drive’s local lock feature has been activated.

What are the primary causes of A5015 fault?

The root causes are an active lock setting in parameter 1606, an energized digital lock input, or a supervisory PLC lock command.

How do I troubleshoot and correct A5015 fault?

Access parameter 1606 through a permitted interface, disable the lock function, and confirm the digital input status on terminal X1A.