A5080 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A5080 alarm in ABB ACS355 drive

The A5080 alarm warns that a start, stop, direction, or speed reference modification was attempted from the keypad while the ABB ACS355 drive was in Remote Control mode. The drive rejects the panel command and continues responding exclusively to external I/O or fieldbus signals.

The ACS355 control logic enforces strict arbitration between Local control (keypad commands) and Remote control (terminal strip X1 or Modbus fieldbus commands). When the top-left status display indicates REM, the microprocessor directs motor modulation and IGBT gating in accordance with external inputs assigned in parameter 1001 (EXT1 COMMANDS) or parameter 1002 (EXT2 COMMANDS). Keypad drive control buttons are deliberately ignored to prevent unsafe operator override of plant safety systems and centralized PLCs.

What Causes A5080 in ABB ACS355?

  1. An operator pressed the keypad START, STOP, or arrow keys while the drive control location was set to REM.
  2. The LOC/REM selection key on the control panel was pressed, but local control switching has been locked out by parameter 1606 (LOCAL LOCK).
  3. An external digital input or PLC fieldbus bit is holding control authority and inhibiting local mode transition.
  4. Macro settings in parameter 9902 default to permanent external control without panel authorization.
  5. Keypad button bounce or electrical noise on the panel bus simulating an unexpected start or stop button press.

Step-by-Step Troubleshooting and Solutions

  1. Check the upper-left corner of the Assistant Control Panel display; if it reads REM, press the LOC/REM button once to toggle the drive into LOC mode.
  2. If pressing LOC/REM has no effect, inspect parameter 1606 (LOCAL LOCK); if set to 1 (LOCKED) or mapped to a digital input, change it to 0 (NOT USED).
  3. Verify external start/stop interlocks: if operating in remote mode, issue commands via the proper digital inputs (e.g., terminal DI1) or PLC Modbus control word rather than keypad buttons.
  4. Check parameter group 10 (START/STOP/DIR) and group 11 (REFERENCE SELECT) to confirm source assignments for external control places EXT1 and EXT2.
  5. If local control must remain disabled for plant safety, instruct operators that local keypad start/stop commands are intentionally blocked during automated line operation.

Preventative Maintenance to Avoid A5080 Faults

Provide clear operator signage on control cabinets explaining whether drives operate in Local or Remote automation modes. Configure parameter 1606 systematically across identical production lines to prevent unauthorized local overrides, and maintain clean panel membranes to prevent sticky push buttons from generating unintended keypad inputs.

Frequently Asked Questions (FAQs)

What is the meaning of A5080 fault in ABB ACS355 drive?

The A5080 alarm indicates that an operator attempted to control the drive using keypad buttons while the unit was in Remote control mode.

What are the primary causes of A5080 fault?

The main causes are pressing panel start, stop, or speed keys while in REM mode, or having local control locked out by parameter 1606.

How do I troubleshoot and correct A5080 fault?

Press the LOC/REM button to toggle into local mode, check parameter 1606 settings, or use external terminal inputs to control the drive.