F0035 OUTPUT WIRING fault in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/F0035 OUTPUT WIRING fault in ABB ACS355 drive

The F0035 fault indicates that the ABB ACS355 drive has identified an incorrect power wiring configuration, such as incoming line mains connected to the motor output terminals. The drive halts operation to prevent catastrophic semiconductor breakdown across the inverter power stage.

Before releasing high-frequency PWM switching pulses, the drive microprocessor conducts an internal pre-magnetization test and monitors reverse current leakage across the freewheeling diodes. If line voltage is erroneously landed on motor terminals U2, V2, and W2 instead of supply terminals L1, L2, and L3, full mains potential is impressed across the IGBT bridge. Additionally, on corner-grounded delta supply systems or ungrounded IT networks with lengthy shielded cables, excessive parasitic cable capacitance can trigger false current leakage detections, causing nuisance F0035 trips.

What Causes F0035 in ABB ACS355?

  1. Incoming 3-phase AC supply leads accidentally wired to drive output terminals U2, V2, and W2.
  2. Motor power cables mistakenly connected to drive input supply terminals L1, L2, and L3.
  3. High parasitic capacitive leakage currents caused by long, shielded motor cable runs on corner-grounded delta or IT systems.
  4. Internal drive hardware fault caused by a shorted or degraded freewheeling diode within the IGBT power module.
  5. An EMC filter varistor screw connected while operating on an ungrounded or floating electrical distribution grid.

Step-by-Step Troubleshooting and Solutions

  1. Isolate main incoming power, lock out the panel, and carefully verify physical line and load wiring connections against drive schematics.
  2. Confirm that 3-phase line power connects strictly to input terminals L1, L2, and L3, and motor cables connect strictly to U2, V2, and W2.
  3. If running on an ungrounded IT system or corner-grounded delta network, remove the EMC filter grounding screw to disconnect internal surge capacitors from ground.
  4. Disconnect the motor cable from output terminals U2, V2, and W2 and execute a diode check on the inverter bridge using a digital multimeter in diode mode.
  5. If long motor cables (greater than 30 meters) cause capacitive trips, install an ABB du/dt filter or output reactor to attenuate high-frequency parasitic charging currents.
  6. Verify parameter 3023 (WIRING FAULT); if verified safe on a delta system, adjust supervision settings according to the ABB technical manual.

Preventative Maintenance to Avoid F0035 Faults

Clearly label power line and load conduits inside industrial cabinets to avoid cross-wiring errors during field retrofits. Follow ABB installation guidelines regarding maximum permissible motor cable lengths, and install output chokes on retrofitted systems utilizing legacy or unshielded field cabling.

Frequently Asked Questions (FAQs)

What is the meaning of F0035 fault in ABB ACS355 drive?

The F0035 fault indicates that power wiring is crossed or that excessive cable capacitance mimics an incorrect connection on output terminals.

What are the primary causes of F0035 fault?

The main causes are landing incoming power on motor terminals U2, V2, and W2, or high cable capacitance on delta-grounded networks.

How do I troubleshoot and correct F0035 fault?

Verify line versus motor cable terminations, disconnect the EMC screw on floating networks, and install an output reactor for long cable runs.