F1006 fault in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/F1006 fault in ABB ACS355 drive

The F1006 fault indicates an extension relay output parameter conflict in the ABB ACS355 drive. The drive trips because parameters have been assigned to extension relay outputs while the required MREL-01 module is missing or undetected.

The standard ACS355 base unit contains only one physical relay output (RO1). When parameters configure auxiliary relays RO2, RO3, or RO4, the drive processor continuously polls the expansion slot X3 interface bus. If the optional MREL-01 extension module is disconnected or fails communication handshakes, the drive trips to prevent unmonitored relay interlocking failures in external safety or process circuits.

What Causes F1006 in ABB ACS355?

  1. Parameters 1402 RELAY OUTPUT 2, 1403 RELAY OUTPUT 3, or 1410 RELAY OUTPUT 4 set to active non-zero functions without an MREL-01 module.
  2. The MREL-01 relay output module is physically unseated or has bent connection pins in slot X3.
  3. Downloading a parameter backup file from a drive that had an extension relay module installed.
  4. Hardware component failure on the internal circuit board of the MREL-01 extension module.
  5. Corrupted relay configuration registers stored in parameter Group 14 RELAY OUTPUTS.

Step-by-Step Troubleshooting and Solutions

  1. Verify whether the physical MREL-01 relay output extension module is installed into expansion slot X3.
  2. If no module is installed, access Group 14 RELAY OUTPUTS and set parameters 1402, 1403, and 1410 to 0 (NOT USED).
  3. If the module is present, isolate power on terminals U1, V1, W1, remove the module, and check interface pins for oxidation or misalignment.
  4. Reseat the MREL-01 module firmly and tighten the grounding screw to ensure solid contact with the drive chassis.
  5. Reapply power and inspect the relay terminal status indicators to confirm proper module detection.

Preventative Maintenance to Avoid F1006 Faults

Confirm that option modules are securely fastened with retaining screws in high-vibration applications, and ensure parameter backups match physical drive hardware configurations before downloading.

Frequently Asked Questions (FAQs)

What is the meaning of F1006 fault in ABB ACS355 drive?

The F1006 fault indicates that extension relay outputs are configured in parameters but the MREL-01 relay module is missing or not detected.

What are the primary causes of F1006 fault?

Primary causes include non-zero settings in parameters 1402, 1403, or 1410 without an MREL-01 module, loose module seating, or parameter file mismatches.

How do I troubleshoot and correct F1006 fault?

Set parameters 1402, 1403, and 1410 to zero if no module is used, or re-seat the MREL-01 hardware firmly in option slot X3.