The F1007 fault indicates that fieldbus control has not been activated in the ABB ACS355 drive. The drive trips because operational control words or reference speeds have been assigned to fieldbus sources while the communication protocol remains disabled.
When start/stop or reference parameters are pointed to fieldbus commands (COMM), the drive’s internal supervisory controller requires an active fieldbus protocol handler. If parameter 9802 COMM PROT SEL is set to 0 (NOT SEL), the drive detects an orphaned control loop. Inverter pulse-width modulation remains strictly inhibited, preventing IGBT firing across terminals U2, V2, W2 to avoid uncontrolled or uncommanded motor motion.
What Causes F1007 in ABB ACS355?
- Parameter
1001 EXT1 COMMANDSor1002 EXT2 COMMANDSassigned toCOMMwhile fieldbus is deactivated. - Parameter
1103 REF1 SELECTor1106 REF2 SELECTset toCOMMwith protocol disabled in parameter9802 COMM PROT SEL. - Run enable parameter
1601 RUN ENABLEconfigured to fieldbus control without active communications. - Keypad parameter download from a networked drive onto a standalone hardwired unit.
- Fieldbus adapter module removed from expansion slot
X3without reconfiguring control command parameters.
Step-by-Step Troubleshooting and Solutions
- Navigate to parameter Group
98 OPTIONSand check parameter9802 COMM PROT SEL. - Set parameter
9802 COMM PROT SELto1 (STD MODBUS)for built-in RS-485 or4 (EXT FBUS)for an external plug-in adapter. - If operating the drive using hardwired digital and analog terminals, change parameter
1001 EXT1 COMMANDSto1 (DI1,2)or2 (DI1P,2P). - Reassign parameter
1103 REF1 SELECTto1 (AI1)or2 (AI2)for analog potentiometer control. - Inspect RS-485 serial wiring on terminal block
X1C(terminals29 B+,30 A-,31 AGND) to ensure proper connection.
Preventative Maintenance to Avoid F1007 Faults
Maintain separate parameter template files for fieldbus-controlled and hardwired standalone drives, and review command source configurations whenever altering machine control wiring.
Frequently Asked Questions (FAQs)
What is the meaning of F1007 fault in ABB ACS355 drive?
The F1007 fault indicates that the drive has commands assigned to fieldbus control but the fieldbus protocol itself has not been activated.
What are the primary causes of F1007 fault?
Primary causes are selecting COMM for start/speed commands while parameter 9802 is set to NOT SEL, or downloading network parameter backups onto standalone drives.
How do I troubleshoot and correct F1007 fault?
Enable the required protocol in parameter 9802 or reassign parameters 1001 and 1103 to physical digital and analog input terminals.