A2002 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2002 alarm in ABB ACS355 drive

The A2002 alarm signifies that the internal DC bus overvoltage controller in the ABB ACS355 drive is actively engaged. The drive alters deceleration rates dynamically to prevent bus overvoltage from exceeding hardware trip thresholds.

During aggressive motor braking, kinetic mechanical energy regenerates through the inverter bridge diodes and pumps surplus voltage into the intermediate DC bus capacitors. The ACS355 controller intervenes by restricting further deceleration braking torque to protect internal bus capacitors and power electronics, which can lead to extended stop times or run-away deceleration profiles.

What Causes A2002 in ABB ACS355?

  1. Deceleration ramp configured too short in parameter 2203 DECELER TIME 1 or parameter 2206 DECELER TIME 2.
  2. High-inertia mechanical load back-feeding excessive regenerative energy into the drive.
  3. Static utility overvoltage or transient line surges occurring across AC input terminals R, S, T (or L, N).
  4. Absence, sizing error, or open circuit in the optional dynamic braking resistor connected across BRK+ / BRK-.
  5. Unintended overvoltage controller enable/disable parameter mismatch under fluctuating power networks.

Step-by-Step Troubleshooting and Solutions

  1. Extend deceleration ramps by increasing the values in parameter 2203 DECELER TIME 1 and parameter 2206 DECELER TIME 2.
  2. Measure steady-state and peak AC incoming line voltages with a True-RMS meter to confirm supply stability within nominal drive tolerance.
  3. Verify the internal overvoltage control function is set active in parameter 2005 OVERVOLT CTRL to permit dynamic deceleration stretching.
  4. Inspect external dynamic brake resistor resistance and thermal switch wiring across terminals BRK+ and BRK-.
  5. Check parameter group 27 BRAKE CHOPPER settings if an external braking unit is deployed for high-inertia deceleration.

Preventative Maintenance to Avoid A2002 Faults

Regularly inspect incoming line transient voltage suppression devices, ensure braking resistor cages are free of lint and dust accumulation, and re-evaluate ramp rates whenever conveyor or fan mechanical inertia properties change.

Frequently Asked Questions (FAQs)

What is the meaning of A2002 fault in ABB ACS355 drive?

It indicates that the drive intermediate DC bus voltage has climbed too high and the overvoltage controller is actively limiting braking rate.

What are the primary causes of A2002 fault?

It occurs when high inertia regenerates power during rapid deceleration or when severe line voltage spikes destabilize the intermediate DC link.

How do I troubleshoot and correct A2002 fault?

Lengthen parameter 2203 deceleration time, measure main line voltages, and ensure the dynamic braking chopper resistor is operating correctly.