A2004 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2004 alarm in ABB ACS355 drive

The A2004 alarm informs the operator that a commanded change of motor rotation direction is actively locked out and disallowed. The ABB ACS355 drive ignores the reverse or forward command to protect mechanical machinery from counter-rotation.

When the drive control circuitry receives a run command demanding an opposite rotational direction from what is authorized, software interlocks prevent the inverter stage from changing phase sequence modulation. The IGBT gate drivers maintain current rotational orientation or hold zero speed, safeguarding equipment such as screw compressors, centrifugal pumps, and gear reducers from mechanical destruction.

What Causes A2004 in ABB ACS355?

  1. Control logic or digital input issuing a reverse command while parameter 1003 DIRECTION is configured to 1 (FORWARD).
  2. Control system demanding a forward run command while parameter 1003 DIRECTION is locked strictly to 2 (REVERSE).
  3. PLC fieldbus communications transmitting a negative reference or reverse direction bit over Modbus RTU contrary to drive permissions.
  4. Defective wiring or electrical cross-talk activating digital input terminal DI2 or DI3 assigned to direction switching.
  5. Improper application macro selection in parameter 9902 APPLIC MACRO that locks physical rotation boundaries.

Step-by-Step Troubleshooting and Solutions

  1. Review the rotational requirement of the machinery and update parameter 1003 DIRECTION to 3 (REQUEST) if bi-directional operation is required.
  2. Check PLC program logic and network control words in parameter group 01 OPERATING DATA to ensure the correct direction bit is sent.
  3. Measure 24V DC control signal levels across digital input terminals DI1 through DI5 against common terminal GND.
  4. Inspect parameter 1001 EXT1 COMMANDS and parameter 1002 EXT2 COMMANDS to verify assigned run and direction source selections.
  5. Audit the operator panel direction push button settings if local control mode is selected via the LOC/REM key.

Preventative Maintenance to Avoid A2004 Faults

Document parameter lockouts in mechanical system records, maintain shielded control wiring to prevent stray induction voltage on direction inputs, and ensure PLC routine handshakes align with drive parameter configurations.

Frequently Asked Questions (FAQs)

What is the meaning of A2004 fault in ABB ACS355 drive?

It indicates that the drive has rejected a command to change rotational direction because internal parameter locks restrict motion.

What are the primary causes of A2004 fault?

This alarm is caused by parameter 1003 restricting movement to forward or reverse, conflicting PLC direction bits, or miswired control terminals.

How do I troubleshoot and correct A2004 fault?

Check parameter 1003 settings, verify whether bi-directional rotation is permitted, and inspect direction digital inputs and fieldbus words.