A2006 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2006 alarm in ABB ACS355 drive

The A2006 alarm indicates that analog input AI1 has dropped below the minimum permissible supervision threshold. The drive triggers this warning to prevent erratic velocity changes or unexpected motor stalls caused by broken transducer wiring.

In standard analog current loops operating between 4–20 mA, an input dropping below 2 mA indicates a broken conductor or sensor failure rather than a genuine zero command. When the analog sampling circuit detects this drop, the processor evaluates parameter 3001 AI. While an alarm condition keeps the IGBT bridge modulating according to safety fallback speeds (such as constant speed or last speed), failure to rectify the loop signal can lead to unstable motor operation or process tripping.

What Causes A2006 in ABB ACS355?

  1. Broken, disconnected, or corroded signal conductor on analog input terminal 2 (AI1) or common terminal 3 (GND).
  2. External process transmitter (e.g., pressure, flow, or potentiometer) unpowered or suffering an internal hardware defect.
  3. Signal level dropping below the value established in parameter 3021 AI1 FAULT LIMIT.
  4. Jumper J1 incorrectly set to voltage mode (0–10 V) while the external transmitter is supplying a current loop (4–20 mA), or vice versa.
  5. Power supply drop or failure on auxiliary output terminal 9 (+24V) feeding passive 2-wire field sensors.

Step-by-Step Troubleshooting and Solutions

  1. Measure the analog input signal across terminals 2 (AI1) and 3 (GND) using a calibrated digital multimeter in series (for mA) or parallel (for V).
  2. Check hardware jumper J1 position on the control board to verify whether it matches the selected signal type (current vs. voltage).
  3. Review parameter 3021 AI1 FAULT LIMIT; ensure the threshold is set appropriately (typically 10% or 20% corresponding to 2 mA or 4 mA).
  4. Evaluate parameter 3001 AI to verify if the drive is set to alarm (FAULT, CONST SP 7, or LAST SPEED).
  5. Test the +24 VDC sensor power supply on terminal 9 relative to terminal 11 (GND) to confirm adequate transducer excitation voltage.

Preventative Maintenance to Avoid A2006 Faults

Inspect analog signal terminals annually for mechanical tightness, verify that twisted-shielded instrumentation cables are properly grounded at the drive chassis end only, and periodically calibrate process transducers to prevent output signal drift.

Frequently Asked Questions (FAQs)

What is the meaning of A2006 fault in ABB ACS355 drive?

This alarm warns that analog input channel 1 has fallen beneath the safety signal limit defined in the drive supervision parameters.

What are the primary causes of A2006 fault?

Common causes include open-circuit transducer loops, broken signal cables on terminal 2, unpowered transmitters, or incorrect hardware jumper configurations.

How do I troubleshoot and correct A2006 fault?

Measure the milliamp input signal at the drive terminals, confirm parameter 3021 thresholds, and verify that the 24V auxiliary power is healthy.