A2008 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2008 alarm in ABB ACS355 drive

The A2008 alarm indicates a loss of serial communication between the drive main control board and the mounted control panel. This protection mechanism alerts the operator when local control authority has been interrupted.

The ACS355 interfaces with either the Basic Control Panel or Assistant Control Panel via a front-facing modular RJ45 interface. When parameter 3002 PANEL COMM ERR is active and the panel is selected as the controlling location (in LOCAL mode or under REMOTE mode via parameter group 10 START/STOP/DIR or group 11 REFERENCE SELECT), missing polling telegrams trigger the supervision timer. The drive maintains its output frequency or transitions to a preset state while logging the alarm.

What Causes A2008 in ABB ACS355?

  1. Physical disconnection, loose seating, or vibration dislodging the control panel from its front door cradle or drive bezel.
  2. Damaged pins, dirt, or oil contamination within the modular RJ45 connector socket.
  3. Defective panel extension cable or high electrical noise coupling onto remote door-mounting kits.
  4. Control panel hardware malfunction or internal firmware handshake failure during high electrical transients.
  5. Drive programmed to take start/stop or frequency references from the keypad while the keypad is unplugged.

Step-by-Step Troubleshooting and Solutions

  1. Firmly unseat and re-insert the control panel into the mounting platform to ensure all physical contact pins engage properly.
  2. Inspect the RJ45 male and female connector pins on both the keypad and the drive chassis for bending, corrosion, or contamination.
  3. If a remote mounting platform kit is used, inspect the patch cable for damage and test continuity on all 8 conductor cores.
  4. Review parameter 3002 PANEL COMM ERR to verify whether the supervision action is configured for FAULT or CONST SP 7.
  5. Check parameters in group 10 (START/STOP/DIR) and group 11 (REFERENCE SELECT); if control is handled via terminal I/O or fieldbus, change settings from PANEL to DI or COMM.

Preventative Maintenance to Avoid A2008 Faults

Ensure cabinet door-mounted keypads use high-grade shielded patch cables routed away from inverter output conductors, check panel latching clips during maintenance rounds, and keep the RJ45 port cover installed when no keypad is connected.

Frequently Asked Questions (FAQs)

What is the meaning of A2008 fault in ABB ACS355 drive?

It signifies that serial data transmission between the drive processing unit and the attached operator keypad has been disrupted.

What are the primary causes of A2008 fault?

The main causes are a physically loose keypad, bent RJ45 connector pins, damaged door-mount extension cables, or reference configuration errors.

How do I troubleshoot and correct A2008 fault?

Reseat the panel into its cradle, verify the condition of the RJ45 cable, and review Group 10 and 11 control source parameters.