The A2026 alarm indicates an input phase loss condition caused by high intermediate DC circuit voltage ripple exceeding 14% of nominal DC voltage. The ABB ACS355 activates this supervisory warning to alert operators to line power imbalances before capacitor damage occurs.

In three-phase drive operation, a balanced six-pulse diode bridge rectifier maintains a smooth intermediate DC link voltage. If one incoming AC supply phase opens or sags severely, the rectification switches into single-phase mode. This causes excessive voltage ripple across the DC bus capacitors, forcing high thermal stress onto the capacitor bank, stressing bridge diodes, and increasing electromagnetic noise across the inverter switching modulation.

What Causes A2026 in ABB ACS355?

  1. Blown or high-resistance AC line fuse on incoming power terminals U1, V1, W1.
  2. Severe supply phase voltage unbalance exceeding 3% across the facility distribution transformer.
  3. Loose wire termination, pitted disconnect switch contacts, or dropped phase upstream of the VFD.
  4. Internal input rectifier diode bridge failure leading to half-wave conduction.
  5. Excessive single-phase loading on the facility circuit, or aggressive tripping configured in parameter 3016 SUPPLY PHASE.

Step-by-Step Troubleshooting and Solutions

  1. Measure AC line voltages across terminals U1-V1, V1-W1, and U1-W1 under loaded operational conditions.
  2. Disconnect power, lock out the drive, and test continuity across all upstream input branch fuses.
  3. Inspect and torque all incoming electrical lugs on line terminals U1, V1, W1 to nominal tightening values.
  4. Evaluate parameter 3016 SUPPLY PHASE to confirm whether protection is set to FAULT (1) or NO (0).
  5. Perform an input rectifier diode test with a multimeter in diode mode across input terminals and DC terminals BRK+ / UDC-.

Preventative Maintenance to Avoid A2026 Faults

Perform semi-annual thermographic scans on power disconnects and fuse holders to identify phase hotspots, and deploy line reactors to dampen incoming power spikes and smooth DC link ripple current.

Frequently Asked Questions (FAQs)

What is the meaning of A2026 fault in ABB ACS355 drive?

It warns that the DC bus ripple has exceeded 14 percent due to an absent or severely degraded incoming three-phase supply line.

What are the primary causes of A2026 fault?

Primary root causes include blown mains branch fuses, loose supply wiring terminals, damaged rectifier diodes, or severe phase voltage imbalance.

How do I troubleshoot and correct A2026 fault?

Measure input phase voltages, inspect upstream line fuses, verify terminal tightness, and examine parameter 3016 supervisory settings.