The A5011 alarm alerts operators that a manual command was given from the keypad while the drive is operating under external remote control. This interlock prevents conflicting operation when plant automation controls the drive.
The ACS355 operates under two distinct command hierarchies: Local (LOC) and Remote (REM). When the drive is in REM, motor speed reference and start/stop signals are governed strictly by I/O terminals (such as digital inputs DI1 through DI5) or fieldbus network commands. If an operator presses the keypad Start, Stop, or Direction key, the control architecture blocks the command from influencing IGBT firing angles, flashing alarm code A5011 on the display for 2 to 3 seconds while maintaining uninterrupted production run states.
What Causes A5011 in ABB ACS355?
- Pressing keypad Start, Stop, or arrow keys while the drive status indicator displays
REMmode. - Local control mode locked out by automation logic through parameter
1606 LOCAL LOCK. - Control logic configured to execute exclusively from external command groups
10 (START/STOP/DIR)and11 (REFERENCE SELECT). - Operator attempting to change motor direction manually from the panel while remote control is active.
- Unintended key presses on door-mounted keypads during routine operator panel inspections.
Step-by-Step Troubleshooting and Solutions
- Press the
LOC/REMkey on the control panel to switch the drive operating mode from remote status to local status (LOC). - Check parameter
1606 LOCAL LOCK; verify that it is set to0 = NOT SELto allow switching between local and remote authority. - Review parameter
1001 EXT1 COMMANDSand1002 EXT2 COMMANDSto confirm which external terminals govern running sequences. - Inspect digital input terminal
8 (DI1)through terminal12 (DI5)using a DC voltmeter (24 VDClogic) to identify active external run commands. - If remote control must be retained, provide start, stop, and speed adjust commands exclusively via external field wiring or the supervisory PLC.
Preventative Maintenance to Avoid A5011 Faults
Train operators on the function of the LOC/REM toggle key, label cabinet doors clearly regarding whether local manual control is permitted, and restrict local overrides on mission-critical automated lines using parameter 1606.
Frequently Asked Questions (FAQs)
What is the meaning of A5011 fault in ABB ACS355 drive?
It is an operational warning signaling that a panel start, stop, or speed command was rejected because the drive is set to remote control mode.
What are the primary causes of A5011 fault?
The primary cause is pressing keypad control buttons while in REM mode, having parameter 1606 locked, or relying on active external PLC inputs.
How do I troubleshoot and correct A5011 fault?
Press the LOC/REM button to transfer command authority to the local keypad, or issue machine commands through external terminal I/O.