A5013 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A5013 alarm in ABB ACS355 drive

The A5013 alarm indicates that local keypad control is inhibited because an active safety interlock, emergency stop, or 3-wire stop circuit is engaged. The drive blocks keypad starting to guarantee personnel and system safety.

The ACS355 control logic continuously evaluates safety-critical interlocks before allowing pulse-width modulation gate firing. When an active emergency stop command is assigned via parameter 2109 EMERG STOP SEL, a 3-wire stop circuit is open, or a start inhibit function is asserted, the drive logic disables the local start button. The intermediate DC bus remains charged, but gate driver signals to the output IGBTs are securely withheld until external interlocks are completely satisfied and reset.

What Causes A5013 in ABB ACS355?

  1. An active, latched emergency stop pushbutton wired into digital inputs (e.g., terminal DI1 through DI5 assigned in parameter 2109).
  2. The drive is programmed for 3-wire control macros (e.g., parameter 1001 EXT1 COMMANDS set to 3-WIRE) and the stop contact is open.
  3. Start inhibit feature enabled in parameter 2108 START INHIBIT preventing immediate restart after fault clearance or line power restoration.
  4. Safe Torque Off (STO) circuit on dual-channel terminals X1C (IN1, IN2, OUT, SGND) is de-energized or open.
  5. Supervisory PLC interlock holding an open run enable signal on terminal 12 (DI4) or 13 (DI5) via parameter 1601 RUN ENABLE.

Step-by-Step Troubleshooting and Solutions

  1. Inspect field emergency stop pushbuttons; physically release and reset any tripped mushroom-head switches wired to the drive.
  2. Check parameter 2109 EMERG STOP SEL; identify which digital input controls emergency stop and measure DC voltage across that terminal and +24V.
  3. If 3-wire control is configured in parameter 1001, verify that the normally closed (NC) stop contact on terminal 8 (DI1) or 9 (DI2) is closed.
  4. Review parameter 2108 START INHIBIT; if continuous auto-start is required by the process following power recovery, set to 0 = OFF.
  5. Inspect dual-channel STO terminals on connector X1C; verify 24 VDC is present across IN1-SGND and IN2-SGND jumpers.

Preventative Maintenance to Avoid A5013 Faults

Perform regular functional safety proof tests on all emergency stop buttons and wire-break interlocks, inspect terminal strip screw torques on connector X1C, and verify that safety relays maintain clean, low-resistance dry contact outputs.

Frequently Asked Questions (FAQs)

What is the meaning of A5013 fault in ABB ACS355 drive?

It indicates that local panel start is disabled because an external emergency stop, 3-wire stop circuit, or safety interlock is currently active.

What are the primary causes of A5013 fault?

Common root causes include a tripped emergency stop button, an open 3-wire stop contact, an active STO input, or start inhibit parameter settings.

How do I troubleshoot and correct A5013 fault?

Release the emergency stop switch, verify continuity on your 3-wire stop circuit, and check parameter 2109 and parameter 2108 configurations.