F0014 fault in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/F0014 fault in ABB ACS355 drive

The F0014 fault indicates that the external fault 1 supervision circuit has tripped on the ABB ACS355 drive. The drive shuts down motor output modulation instantly in response to a discrete open or closed contact from an external protective device.

The ACS355 provides configurable digital input channels to integrate external safety and process monitoring devices directly into the drive control architecture. When the dedicated external fault input transitions into an active trip state, the main microprocessor terminates gate drive signals to the output inverter bridge. This action cuts motor torque immediately, allowing the motor to coast to a stop and preventing process equipment damage or catastrophic mechanical failure.

What Causes F0014 in ABB ACS355?

  1. Tripped external safety device (such as a motor thermal overload switch, vibration sensor, or oil pressure switch).
  2. Broken, disconnected, or loose 24V DC control wiring on the digital input assigned in parameter 3003 EXTERNAL FAULT 1.
  3. Digital input assigned to parameter 3003 receiving an unintended trip signal due to inverted logic configuration.
  4. Transient electrical noise or high induction voltage on digital input terminal lines DI1 through DI5.
  5. Interruption or voltage sag on the auxiliary internal +24V DC power supply rail feeding the control terminals.

Step-by-Step Troubleshooting and Solutions

  1. Check parameter 3003 EXTERNAL FAULT 1 to identify which digital input terminal (e.g., DI1–DI5) is assigned to this fault.
  2. Inspect the external protective device connected to that input to determine why it tripped, and clear the field condition.
  3. Measure DC voltage across the assigned digital input terminal and common terminal GND (should read 24V DC in normal state).
  4. Check control terminal screws on terminal strip X1A and tighten any loose wire clamps.
  5. If external fault protection is not required, change parameter 3003 EXTERNAL FAULT 1 to NOT SEL (0).

Preventative Maintenance to Avoid F0014 Faults

Use shielded twisted-pair cables for external sensor loops, ground shield drains at the drive chassis only, and regularly test external thermal and pressure contacts to confirm positive mechanical switching.

Frequently Asked Questions (FAQs)

What is the meaning of F0014 fault in ABB ACS355 drive?

It indicates that an external process protection device wired to a digital input has opened its contact and triggered a drive shutdown.

What are the primary causes of F0014 fault?

This fault is caused by a tripped external sensor, loose 24V DC control wiring, incorrect parameter 3003 assignment, or control power drops.

How do I troubleshoot and correct F0014 fault?

Identify the assigned digital input in parameter 3003, inspect the external sensor and wiring continuity, and reset the field device.