The F0015 fault indicates that the secondary external fault 2 protection circuit has triggered on the ABB ACS355 drive. The drive shuts down PWM output gating to isolate the motor from the load upon receiving an external hardware trip signal.
Configured through parameter 3004 EXTERNAL FAULT 2, this supervision channel monitors secondary auxiliary field hardware such as bearing temperature relays, lube oil flow interlocks, or cabinet cooling fan switches. When the monitored circuit interrupts the signal path, the ACS355 processor executes an instantaneous output shutdown. By terminating inverter modulation, the drive eliminates regenerative and driving torque, safeguarding connected machinery from running under hazardous conditions.
What Causes F0015 in ABB ACS355?
- Tripped secondary auxiliary device (such as an airflow switch, lube pump interlock, or safety guard contact).
- Open circuit, broken conductor, or loose terminal screw in the wiring loop connected to digital input terminals
DI1–DI5. - Incorrect source selection configured in parameter
3004 EXTERNAL FAULT 2. - Failure of an external auxiliary 24V DC power relay supplying the status contact.
- Electromagnetic interference (EMI) inducing transient false trips onto unshielded control wiring runs.
Step-by-Step Troubleshooting and Solutions
- Check parameter
3004 EXTERNAL FAULT 2using the control panel to identify the active input terminal assignment. - Inspect the secondary field device and confirm whether it tripped due to an actual operational fault condition.
- Measure the 24V DC potential across the assigned digital input terminal and common terminal
GNDto confirm continuity. - Check terminal block
X1Awiring connections and torque loose clamp screws. - Disable the function by setting parameter
3004 EXTERNAL FAULT 2toNOT SEL (0)if secondary supervision is unused.
Preventative Maintenance to Avoid F0015 Faults
Verify that secondary auxiliary interlock switches are tested during regular maintenance shutdowns, maintain clean and dust-free sensor enclosures, and route control cables through separate conduit from AC power feeders.
Frequently Asked Questions (FAQs)
What is the meaning of F0015 fault in ABB ACS355 drive?
It indicates that a secondary external monitoring device wired to a digital input has opened its circuit and shut down the drive.
What are the primary causes of F0015 fault?
This fault occurs when secondary safety switches trip, field control wiring breaks, or parameter 3004 is configured to an unpowered input.
How do I troubleshoot and correct F0015 fault?
Review the input assignment in parameter 3004, inspect external sensor operation, check 24V DC terminal voltage, and reset the sensor.