A791 alarm in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/A791 alarm in ABB ACS380 drive

Warning A791 in the ABB ACS380 drive indicates an issue with the dynamic braking circuit, signifying that the external brake resistor is broken, open-circuit, or not connected. The drive issues this warning to alert operators that dynamic braking capability is offline.

During regenerative motor deceleration or overhauling mechanical loads, kinetic energy converts into electrical energy and flows back through the inverter bridge into the intermediate DC circuit, raising bus voltage. The ACS380 includes an internal dynamic brake chopper transistor that switches this excess power across terminals R+ and R- into an external power resistor. The drive tests braking circuit integrity and resistor continuity. If the resistor has burned open, disconnected, or exhibits high terminal resistance, dynamic energy cannot dissipate, risking overvoltage trips and loss of controlled deceleration.

What Causes A791 in ABB ACS380?

  1. External brake resistor disconnected or not wired to intermediate DC braking terminals R+ and R-.
  2. Thermal overload burnout resulting in an open-circuit dynamic brake resistor element due to excessive braking cycles.
  3. Tripped external thermal overload switch wired in series with the brake resistor or open safety thermostat contacts.
  4. Loose, corroded, or improperly torqued terminal block connections on the dynamic braking terminal interface.
  5. Incorrect brake chopper configuration settings in parameter group 43 Brake chopper while braking control is enabled.

Step-by-Step Troubleshooting and Solutions

  1. Isolate input AC power, wait five minutes for DC capacitors to discharge below 50V DC, and verify brake resistor physical presence.
  2. Disconnect brake resistor wires from drive terminals R+ and R- and measure resistance with a calibrated ohmmeter.
  3. Verify the measured ohmic value matches the design specification and falls within the minimum/maximum resistance ratings in the ACS380 hardware manual.
  4. Inspect external resistor thermal overload switches or bi-metal thermostats to ensure circuit continuity has not tripped open.
  5. Review parameter group 43 Brake chopper, specifically parameter 43.06 Brake resistor resistance and 43.07 Brake resistor thermal capacity.

Preventative Maintenance to Avoid A791 Faults

Inspect dynamic braking resistor enclosures every six months for accumulated industrial debris, restricted convection cooling louvers, and thermal discoloration. Check resistor terminal lug torque tightness and verify that external thermal overload safety switches are properly integrated into the drive control interlock circuit.

Frequently Asked Questions (FAQs)

What is the meaning of A791 fault in ABB ACS380 drive?

The A791 warning signals that the dynamic brake resistor circuit is broken, disconnected, or displaying an open-circuit condition during supervision.

What are the primary causes of A791 fault?

Primary causes are missing resistor wiring, a burned-out open resistor element, an open thermal safety switch, or loose braking terminal screws.

How do I troubleshoot and correct A791 fault?

Measure the resistor resistance across terminals with an ohmmeter, inspect thermal overload switches, verify cable connections, and check parameter group 43.