The AFE1 alarm indicates that an Emergency Stop command via the OFF2 control mode has been asserted on the ABB ACS380 drive. It notifies operators that the drive has received a coast-to-stop safety instruction and disabled output power.
Under an Emergency Stop OFF2 condition, the drive control unit instantly cuts gate firing pulses to the output IGBT semiconductor bridge. The intermediate DC bus voltage remains charged, but the motor is electrically decoupled from active PWM flux control, allowing the driven mechanical load to coast to an unbraked standstill under natural friction.
What Causes AFE1 in ABB ACS380?
- Actuation or latching of an external Emergency Stop pushbutton, safety pull cord, or interlock barrier.
- An open circuit, disconnected wire, or loose screw terminal on the digital input assigned to the e-stop circuit.
- Fieldbus master PLC broadcasting an Emergency Stop OFF2 command bit within the cyclic Control Word.
- Incorrect source selection configured in parameter
21.05 Emergency stop source. - Parameter
21.04 Emergency stop modeconfigured for OFF2 (coast stop) when an active emergency command is triggered.
Step-by-Step Troubleshooting and Solutions
- Ensure personnel safety around the driven machine, then inspect and reset all physical emergency stop pushbuttons to the normal run state.
- Check parameter
21.05 Emergency stop sourceto verify which physical digital input or fieldbus control word bit commands the e-stop. - Measure DC voltage on the assigned digital input terminal (e.g.,
DI1throughDI6); confirm that a healthy24V DCsignal is present. - Inspect safety relay outputs and contactor feedback contacts linked in series with the e-stop input channel.
- Disconnect motor connections and perform a
500V DCinsulation megger test on motor terminalsT1, T2, T3to ensure ground faults are not destabilizing the control power supply rail.
Preventative Maintenance to Avoid AFE1 Faults
Conduct monthly functional audits of all emergency stop buttons and safety contact blocks to detect mechanical contact sticking. Ensure dual-channel safety relays are tested regularly and that emergency stop control wiring remains shielded from high-power inverter noise.
Frequently Asked Questions (FAQs)
What is the meaning of AFE1 fault in ABB ACS380 drive?
It is an emergency stop alert indicating that an OFF2 command has forced the drive to cut motor power and coast to a stop.
What are the primary causes of AFE1 fault?
Primary causes include depressed emergency stop pushbuttons, broken safety circuit wiring, PLC fieldbus stop bits, and improper parameter settings in 21.05.
How do I troubleshoot and correct AFE1 fault?
Release the tripped emergency stop button, confirm 24V DC at the terminal designated in parameter 21.05, and clear the run command to reset.