AFEA alarm in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/AFEA alarm in ABB ACS380 drive

Warning AFEA in the ABB ACS380 drive indicates that the Enable Start signal is missing while a run or start command is active. The drive microprocessor blocks inverter modulation to prevent motor startup until this dedicated hardware or software permissive is satisfied.

The ACS380 incorporates multiple layers of process start permissives to protect automated conveyor lines, agitators, and positioning machinery from accidental startup. When a run command is commanded via local keypad, terminal inputs, or communication fieldbus, the control operating system evaluates parameter 20.19 Enable start command. If this designated input signal is logic low, the drive holds the output IGBT firing stages in a high-impedance state, preventing voltage generation at motor terminals T1/U, T2/V, T3/W. The drive displays warning AFEA to alert operators that the run command cannot be executed because the machine start permissive loop remains open.

What Causes AFEA in ABB ACS380?

  1. The digital input terminal configured in parameter 20.19 Enable start command is de-energized or floating.
  2. External pre-start interlocks, such as lubricant pressure switches, cooling fan air proving sensors, or material chutes, remain open.
  3. Fieldbus control sequence error where the PLC initiates motor speed references before setting the Enable Start bit high.
  4. Loose, disconnected, or oxidized wiring on control terminals DI1 through DI6 or auxiliary power supply terminal +24V.
  5. Parameter 20.19 Enable start command accidentally altered from Not used to an unassigned input during commissioning.

Step-by-Step Troubleshooting and Solutions

  1. Check parameter 20.19 Enable start command to identify the exact digital terminal or communication bit assigned as the start enable.
  2. If assigned to a physical input such as DI2, measure DC voltage between DI2 and DGND using a multimeter to confirm 24V DC is present.
  3. Inspect all upstream mechanical interlocks, flow switches, and process permissives wired in series with the enable start circuit.
  4. If operating under PLC network control, inspect the communication mapping in parameter group 50 Fieldbus adapter and ensure bit sequencing sets Enable Start before Run.
  5. If the application does not require a start enable interlock, set parameter 20.19 Enable start command to Not used.

Preventative Maintenance to Avoid AFEA Faults

Regularly inspect terminal connection tightness on interlock circuits and ensure process switches are free from debris or mechanical binding. Implement robust PLC interlocking logic routines that verify pre-start conditions and display descriptive HMI operator messages before sending start commands to the drive.

Frequently Asked Questions (FAQs)

What is the meaning of AFEA fault in ABB ACS380 drive?

The AFEA warning indicates that the drive has received a motor start command but cannot run because the prerequisite Enable Start permissive signal is missing.

What are the primary causes of AFEA fault?

Primary causes are an open digital interlock switch, missing 24V supply on the enable input, unasserted PLC control bits, or misconfigured parameters.

How do I troubleshoot and correct AFEA fault?

Examine parameter 20.19 to locate the source, measure 24V DC on the assigned digital input terminal, verify external machine interlocks, and reassert the signal.