Fault 6681 in the ABB ACS380 drive indicates an Embedded Fieldbus (EFB) Communication Loss across the EIA-485 serial link. The drive executes a protective shutdown when communication packets from the Modbus RTU master are interrupted longer than the watchdog timeout period.
The ACS380 utilizes an integrated EIA-485 transceiver on control terminal block X5 (terminals 29 B+, 30 A-, and 31 DGND) to exchange cyclic Modbus RTU telemetry with PLCs and SCADA systems. An internal watchdog timer monitored by parameter 58.16 Communication loss time continuously tracks incoming message frames. If cable breakage, electrical noise, or master PLC failure prevents valid packet reception within this time window, the drive asserts fault 6681 according to the response selected in parameter 58.14 Communication loss action. Output PWM gating stops to prevent automated machinery from operating under stale speed commands.
What Causes 6681 in ABB ACS380?
- Physical disconnection, reversed polarity, or broken wiring at EIA-485 serial terminals
29 B+,30 A-, or31 DGND. - The master controller (PLC, HMI, or SCADA) has transitioned to Stop/Offline mode or ceased transmitting cyclic query packets.
- Missing or incorrectly switched bus termination resistors causing signal reflections along the RS-485 transmission line.
- High-voltage electrical noise induced by unshielded motor output power cables running adjacent to serial data lines.
- Baud rate, parity, or node address mismatch between parameter group
58 Embedded fieldbusand the master PLC network profile.
Step-by-Step Troubleshooting and Solutions
- Inspect communication wiring on terminal block
X5; confirm terminal29 B+connects to Data+,30 A-to Data-, and31 DGNDconnects to signal ground. - Check the physical bus termination switch
TERMon the drive; ensure termination is switchedON(120 Ω) only if the drive is the first or final physical node on the network. - Verify communication settings in parameter group
58 Embedded fieldbus: check58.03 Node address,58.04 Baud rate, and58.05 Parityagainst PLC settings. - Measure differential DC voltage across terminals
29and30using a multimeter; in idle state, voltage must measure between0.2V DC and 5.0V DC. - Review parameter
58.14 Communication loss actionand verify parameter58.16 Communication loss timeis not set too fast for the PLC polling cycle.
Preventative Maintenance to Avoid 6681 Faults
Utilize shielded twisted-pair cables rated specifically for RS-485 industrial fieldbuses (characteristic impedance 120 Ω). Ground the cable shield at one end only to eliminate ground loop currents, and route communication lines in dedicated metal conduits separated from 480V motor lines by at least 200 mm.
Frequently Asked Questions (FAQs)
What is the meaning of 6681 fault in ABB ACS380 drive?
The 6681 fault indicates that the drive has lost serial communication with the embedded fieldbus (Modbus RTU) master past the programmed timeout limit.
What are the primary causes of 6681 fault?
Primary causes are broken or reversed EIA-485 serial wiring, an offline PLC master, missing 120-ohm termination resistors, and baud rate setting mismatches.
How do I troubleshoot and correct 6681 fault?
Verify wiring on terminals 29, 30, and 31, confirm master PLC communication status, check group 58 baud rate parameters, and verify termination switch positions.