The 5691 fault code in the ABB ACS380 drive denotes a measurement circuit Analog-to-Digital Converter (ADC) trip. The drive shuts down when internal self-tests detect that the ADC hardware sampling critical voltage and current feedback has failed.
The onboard analog-to-digital converter continuously digitizes analog voltages from current sensors on terminals T1/U, T2/V, T3/W, intermediate DC link voltage in parameter 01.11 DC voltage, and IGBT heatsink thermistors. If the ADC reference voltage drifts or conversion conversions time out, the motor vector control algorithm loses telemetry. Operating without valid current feedback risks unmonitored overcurrent and motor stall; hence, the drive terminates modulation and latches fault 5691.
What Causes 5691 in ABB ACS380?
- Physical component failure or internal degradation of the multi-channel ADC integrated circuit on the power board.
- Failure of internal precision voltage reference diodes feeding the analog sampling circuitry.
- Severe ground loops or high-frequency potential shifts between control ground and terminal
PE. - Moisture condensation or conductive carbon dust creating high-impedance bridges across ADC surface-mount pins.
- Internal power rail sag on the auxiliary
+5Vor+3.3Vanalog conversion bus.
Step-by-Step Troubleshooting and Solutions
- Disconnect power from supply terminals
L1, L2, L3, wait 5 minutes for the DC link to discharge, and perform a complete line power reboot. - Access parameter group
01 Actual valuesand examine parameters01.07 Motor currentand01.11 DC voltage; check for erratic, overflowing, or frozen values while at standstill. - Inspect protective earth bonding to terminal
PE; verify low ground impedance to ensure stray ground currents are not corrupting analog baselines. - Disconnect field motor cabling from terminals
T1/U, T2/V, T3/Wand re-test to verify whether external electrical noise causes false conversion trips. - If fault 5691 recurs immediately on an unloaded drive after a cold reboot, the analog measurement hardware is damaged and the drive must be replaced.
Preventative Maintenance to Avoid 5691 Faults
Maintain consistent climate control inside electrical enclosures to prevent temperature-induced component drift and moisture condensation. Verify that all analog sensor cables use twisted-pair shielded conductors grounded at a single point to prevent ground noise injection.
Frequently Asked Questions (FAQs)
What is the meaning of 5691 fault in ABB ACS380 drive?
Fault 5691 indicates that the internal analog-to-digital converter circuit responsible for processing current and voltage feedback has suffered a hardware failure.
What are the primary causes of 5691 fault?
Primary causes include failed ADC converter chips, damaged reference voltage diodes, severe ground loop interference, and conductive circuit board contamination.
How do I troubleshoot and correct 5691 fault?
Perform a complete cold reboot, verify actual feedback readings in parameter group 01, check protective grounding, and replace the drive if the error persists.