The 5697 fault indicates that the internal DC pre-charge feedback confirmation signal is missing in the ABB ACS380 drive. The drive control system asserts this shutdown when it fails to verify that the intermediate charging bypass circuit has successfully closed.
Upon power application, the ACS380 directs incoming current through internal current-limiting resistors to charge the intermediate DC bus capacitors smoothly. Once the bus reaches operating voltage, the drive commands the bypass relay or thyristor to close and expects an immediate feedback confirmation signal. If this signal is absent, the drive trips to prevent running full inverter load through the pre-charge resistors, which would otherwise burn out within seconds.
What Causes 5697 in ABB ACS380?
- Defective internal pre-charge bypass relay, worn contacts, or failed bypass relay actuator coil.
- Broken, disconnected, or damaged feedback wiring harness between the charging circuit and control board.
- Severe incoming line voltage sag or phase loss across terminals
L1, L2, L3during power-up. - Open-circuit soft-charge resistor preventing the intermediate DC circuit from reaching target potential.
- Failure of the internal switch-mode power supply (SMPS) rail feeding the charging feedback optocoupler.
Step-by-Step Troubleshooting and Solutions
- Measure three-phase AC input voltage across terminals
L1-L2, L2-L3, L1-L3with a multimeter to verify line balance and stability. - Monitor parameter
01.11 DC voltageon the assistant control panel during power energization to confirm that DC bus voltage reaches1.35 to 1.41times input line RMS. - Listen for the mechanical click of the internal charging bypass relay approximately two seconds after switching on mains power.
- De-energize incoming power, wait until the DC bus drops below
50V DC, and cycle power to verify if the fault is repeatable. - If input line voltages are stable and the DC bus charges fully but fault 5697 persists, replace the power unit or complete drive.
Preventative Maintenance to Avoid 5697 Faults
Avoid rapid, repetitive power cycling of the main line contactor; allow at least three minutes between sequential power-ups to allow pre-charge resistors and relays to cool. Ensure line supply voltages remain within standard specifications (nominal ±10%) and keep cabinet humidity non-condensing.
Frequently Asked Questions (FAQs)
What is the meaning of 5697 fault in ABB ACS380 drive?
It indicates that the drive has not received the required feedback confirmation signal from the internal DC bus pre-charge bypass circuit.
What are the primary causes of 5697 fault?
Primary root causes include a failed pre-charge bypass relay, open charging resistors, severe AC line voltage dips during power-up, and damaged feedback detection circuits.
How do I troubleshoot and correct 5697 fault?
Measure three-phase AC input voltages, monitor DC link charging in parameter 01.11, cycle mains power, and replace the drive if the internal feedback hardware has failed.