6685 fault in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/6685 fault in ABB ACS380 drive

The 6685 fault code in the ABB ACS380 drive indicates an EFB fault 2 condition. This trip represents a protocol-specific application fault generated by the embedded fieldbus subsystem, typically triggered by communication frame corruption or receive queue overruns.

When the drive is commanded over an embedded serial network such as Modbus RTU, the UART serial receiver processes high-speed incoming packet frames. If severe electrical noise or grounding differentials induce framing errors, buffer overflows, or parity mismatches, the communication stack fails to parse command messages. To prevent the motor from running on stale reference speeds or corrupted torque limits, the drive terminates IGBT switching and latches fault 6685.

What Causes 6685 in ABB ACS380?

  1. Severe electrical noise or missing RS-485 termination resistors causing communication framing errors.
  2. Baud rate or character framing format mismatch between the PLC master and the drive EFB port.
  3. Excessive query polling frequency from the PLC master overflowing the drive internal receive buffer.
  4. Ground potential differences between networked devices corrupting differential serial line voltages.
  5. Communication timeout triggered according to parameter 58.14 Communication loss action.

Step-by-Step Troubleshooting and Solutions

  1. Verify that RS-485 bus termination switches are set to ON strictly at the two physical ends of the serial trunk line and set to OFF on intermediate drives.
  2. Ensure parameter 58.04 Baud rate and parameter 58.05 Parity match the PLC communication port configuration.
  3. Inspect fieldbus cabling; verify that shielded twisted-pair wire is used and the shield is clamped 360 degrees to terminal PE.
  4. Increase the communication loss delay timer in parameter 58.16 Communication loss time to prevent nuisance trips during momentary bus traffic spikes.
  5. Reduce the polling frequency on the master PLC to ensure the drive communication buffer is not overwhelmed by rapid cyclic requests.

Preventative Maintenance to Avoid 6685 Faults

Routinely inspect RS-485 communication line terminations and measure line bias voltages with a digital multimeter. Maintain continuous physical separation between high-voltage motor output cabling and low-voltage serial communication lines inside cable trays.

Frequently Asked Questions (FAQs)

What is the meaning of 6685 fault in ABB ACS380 drive?

Fault 6685 is a protocol application error indicating that the embedded fieldbus interface encountered framing errors, buffer overruns, or serial communication failure.

What are the primary causes of 6685 fault?

Primary causes include missing RS-485 termination resistors, excessive PLC polling rates, baud rate mismatches, electrical noise, and improper cable shield grounding.

How do I troubleshoot and correct 6685 fault?

Verify bus termination switch settings, check baud rate and parity in parameter group 58, ensure shielded cables are grounded to PE, and adjust timeout parameter 58.16.