7310 fault in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/7310 fault in ABB ACS380 drive

The 7310 fault code in the ABB ACS380 drive indicates an overspeed trip. The drive trips to protect personnel and machinery when actual motor rotational speed exceeds the programmed maximum operating limit plus internal safety margins.

Overspeed conditions frequently occur under overhauling loads (such as descending hoists or downhill conveyors) or during torque-controlled operation when mechanical load resistance suddenly releases. In this operating region, the motor acts as an unconstrained induction generator, rapidly pumping kinetic energy into the intermediate DC link bus. To prevent severe mechanical stress on motor bearings and protect the inverter against high back-EMF voltages, the drive asserts fault 7310 and opens its output IGBT bridge.

What Causes 7310 in ABB ACS380?

  1. Incorrectly configured speed boundaries set in parameter 30.11 Minimum speed or 30.12 Maximum speed.
  2. Insufficient dynamic braking torque caused by a missing, damaged, or undersized external brake resistor.
  3. Sudden loss of mechanical load while operating in torque reference control mode.
  4. Aggressive speed controller gain settings in parameter 25.02 Speed proportional gain causing severe overshoot.
  5. Overhauling gravitational loads driving the motor shaft faster than synchronous inverter output.

Step-by-Step Troubleshooting and Solutions

  1. Check parameter 30.11 Minimum speed and parameter 30.12 Maximum speed; ensure values correspond with process operating requirements and motor mechanical ratings.
  2. If operating in torque control mode, verify that speed window limits are enabled in parameter group 30 Limits to prevent load runaway.
  3. Inspect the dynamic brake chopper setup; verify that parameter 43.06 Brake chopper enable is active and that the resistor on terminals R+ and R- has proper ohmic resistance.
  4. Tune speed controller gains in parameter group 25 Speed control to dampen transient speed overshoots during step-load changes.
  5. Inspect mechanical holding brakes and mechanical backstops on vertical hoists or inclined conveyors to prevent gravitational overhauling.

Preventative Maintenance to Avoid 7310 Faults

Inspect dynamic braking resistor connections quarterly and ensure heatsinks remain unobstructed. Periodically conduct controlled load-drop tests on hoisting machinery to confirm speed limiters and mechanical brakes engage reliably before overspeed thresholds are breached.

Frequently Asked Questions (FAQs)

What is the meaning of 7310 fault in ABB ACS380 drive?

Fault 7310 indicates that the measured or estimated motor shaft speed has exceeded the safe maximum speed limit configured in parameter group 30.

What are the primary causes of 7310 fault?

Primary causes include gravitational overhauling loads, improper maximum speed settings in parameter 30.12, insufficient braking resistor capacity, and torque control load loss.

How do I troubleshoot and correct 7310 fault?

Verify maximum speed parameters in group 30, inspect dynamic brake resistor operation, tune speed controller gains, and enable speed window limits in torque mode.