F0018 THERM FAIL fault in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/F0018 THERM FAIL fault in ABB ACS550 drive

The F0018 THERM FAIL fault indicates that the internal heatsink temperature sensor circuit inside the ABB ACS550 drive is open or short-circuited. As a critical self-preservation mechanism, the drive halts gating pulses immediately to shield the power section from thermal destruction.

During nominal operation, the drive continuously monitors power module thermal levels using a negative temperature coefficient (NTC) or positive temperature coefficient (PTC) thermistor integrated onto the semiconductor baseplate. If the interface sensing circuit registers an electrical resistance outside calibrated voltage thresholds, PWM modulation terminates instantly. This prevents runaway junction temperatures on the insulated-gate bipolar transistor (IGBT) modules and protects the intermediate DC bus from uncontrolled thermal failure.

What Causes F0018 in ABB ACS550?

  1. Physical open circuit or mechanical fracture of the internal heatsink thermistor lead.
  2. Short circuit across the temperature measurement circuit tracks on the main OINT power board.
  3. Defective signal conditioning analog-to-digital converter on the OMIO control board.
  4. Severe mechanical vibration or thermal cycling fatigue leading to solder joint fractures.

Step-by-Step Troubleshooting and Solutions

  1. Perform a safe power cycle: Isolate line power from terminals U1, V1, W1, wait five minutes for DC bus discharge, and observe if the trip persists upon power restoration.
  2. Inspect internal ribbon cables: Verify that flat ribbon harness connectors between the OMIO control board and the internal OINT board are seated securely.
  3. Evaluate physical environment: Check whether ambient cabinet temperatures violate the standard -15°C to 40°C operating boundary.
  4. Check the motor winding insulation with a 500V or 1000V megger at terminals U2, V2, W2 to ensure severe motor ground faults have not thermally stressed the internal module.
  5. Board-level repair or drive replacement: Because the thermistor is directly embedded within the power module assembly, replace the internal OINT board or replace the complete VFD unit if the internal sensor has permanently failed.

Preventative Maintenance to Avoid F0018 Faults

Preventative maintenance requires regular cleaning of cooling fans, vacuuming airborne debris from the heatsink channels, and maintaining ambient operating environments below 40°C to reduce excessive thermal expansion and contraction cycles on the internal thermistor hardware.

Frequently Asked Questions (FAQs)

What is the meaning of F0018 fault in ABB ACS550 drive?

It indicates that the internal thermistor circuit measuring heatsink temperature has broken or shorted out, forcing the drive to shut down to prevent IGBT overheating.

What are the primary causes of F0018 fault?

The primary causes include internal thermistor sensor breakdown, cracked traces on the internal power interface card, or damaged control ribbon interconnects.

How do I troubleshoot and correct F0018 fault?

Discharge the drive completely, verify internal harness seating, inspect for environmental thermal stress, and replace the internal interface board or the entire drive if the sensor has failed.