A2002 OVERVOLTAGE alarm in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/A2002 OVERVOLTAGE alarm in ABB ACS550 drive

The A2002 OVERVOLTAGE alarm on the ABB ACS550 drive indicates that the internal DC overvoltage controller is actively limiting bus voltage rise. The drive automatically modifies deceleration rates to absorb regenerative energy without allowing the intermediate DC link to reach destructive trip levels.

When a high-inertia load decelerates faster than mechanical friction can dissipate its kinetic energy, the induction motor acts as an electrical generator. This regenerative energy flows backward through the inverter freewheeling diodes into the drive intermediate DC bus capacitors. The ACS550 overvoltage controller detects this rising voltage and automatically overrides the programmed deceleration rate, holding or slowing the ramp to prevent tripping. If regenerative energy overwhelms the capacitive bank and no dynamic braking resistor is installed, the alarm will escalate to an F0002 overvoltage trip.

What Causes A2002 in ABB ACS550?

  1. Deceleration ramp time configured too short in parameter 2203 DECELER TIME 1 or 2206 DECELER TIME 2 for high-inertia equipment.
  2. Static mains utility overvoltage or transient voltage spikes on supply lines caused by capacitor bank switching.
  3. Overhauling mechanical loads such as decline conveyors, uncoilers, or unbalanced industrial blowers driving the rotor.
  4. Missing, open, or incorrectly sized dynamic braking resistor across terminals BRK+ and BRK-.
  5. Disabling overvoltage regulation in parameter 2005 OVERVOLT CTRL while running high-inertia processes without braking choppers.

Step-by-Step Troubleshooting and Solutions

  1. Increase deceleration ramp times in parameter 2203 DECELER TIME 1 and 2206 DECELER TIME 2 to match load inertia.
  2. Verify that parameter 2005 OVERVOLT CTRL is set to 1 (ENABLE) so the software controller actively limits bus rise.
  3. Measure incoming three-phase AC voltage across line terminals U1, V1, W1 to verify it stays within the nominal ±10% tolerance window.
  4. For rapidly stopping or overhauling loads, install an external braking chopper and resistor bank across terminals BRK+ and BRK-.
  5. Verify braking resistor parameters and thermal protection settings configured in parameter group 27 BRAKE CHOPPER.

Preventative Maintenance to Avoid A2002 Faults

Routinely inspect incoming line voltage with a power quality logger, verify dynamic braking resistor thermal integrity, and monitor internal DC bus capacitor health during plant shutdowns.

Frequently Asked Questions (FAQs)

What is the meaning of A2002 alarm in ABB ACS550 drive?

The A2002 alarm indicates the drive DC bus overvoltage regulator is active and extending deceleration ramps to dissipate regenerative energy.

What are the primary causes of A2002 alarm?

Primary causes include fast deceleration ramps, high-inertia overhauling loads, utility voltage surges, and missing dynamic brake resistors.

How do I troubleshoot and correct A2002 alarm?

Increase parameter 2203 deceleration time, enable parameter 2005 overvoltage control, install braking resistors, and verify input mains voltages.