A5014 alarm in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/A5014 alarm in ABB ACS550 drive

The A5014 alarm alerts the operator that control panel motor starting is disabled because an uncleared drive trip condition is active in memory. The drive maintains gating lockout to protect internal power semiconductors and motor windings.

Whenever an electrical trip occurs—such as overcurrent (F0001), DC overvoltage (F0002), or motor earth fault (F0016)—the ACS550 supervisor cuts all IGBT gate driver pulses and latches into a protected lockout state. To prevent hazardous automatic re-starting while underlying short circuits or component overloads persist, the drive processor locks out panel Start commands and flags A5014. The intermediate DC link capacitors remain safely isolated from output terminals U2, V2, W2 until the primary fault is diagnosed, rectified, and acknowledged.

What Causes A5014 in ABB ACS550?

  1. An active, uncleared trip code (e.g., overcurrent, ground fault, or overtemperature) present in drive memory.
  2. Attempting to start the drive from the keypad before pressing the fault reset pushbutton.
  3. Persistent field faults (such as permanent motor winding earth leakage) preventing fault reset completion.
  4. Parameter 1604 FAULT RESET SEL configured to accept resets solely from external digital inputs or fieldbus interfaces.

Step-by-Step Troubleshooting and Solutions

  1. Identify primary fault: Read the active trip message on the display or access parameter 0401 LAST FAULT to diagnose the specific hardware trip condition.
  2. Clear field root cause: Inspect motor cabling, check line supply balances, or allow heatsinks to cool depending on the specific fault indicated.
  3. Acknowledge trip: Press the RESET key on the assistant control panel to clear the active fault state.
  4. Check parameter 1604 FAULT RESET SEL: Verify that fault reset selection permits keypad resets or pulse the assigned digital input terminal (e.g., DI1 through DI6) with 24V DC.
  5. Perform insulation testing: If ground leakage trips persist, isolate terminals U2, V2, W2 and test motor winding insulation with a 1000V DC megger before re-attempting operation.

Preventative Maintenance to Avoid A5014 Faults

Review fault history archives in parameter group 04 FAULT HISTORY during scheduled maintenance, address recurring transient overcurrents promptly, and conduct annual winding insulation megger tests on connected motors.

Frequently Asked Questions (FAQs)

What is the meaning of A5014 alarm in ABB ACS550 drive?

It indicates that local panel starting is blocked because an unacknowledged active drive fault condition exists in memory.

What are the primary causes of A5014 alarm?

Primary causes are uncleared drive trips, attempting to start before resetting faults, continuous short circuits, or misconfigured reset source parameters.

How do I troubleshoot and correct A5014 alarm?

Check parameter zero-four-zero-one for the active fault, correct the physical problem, press the keypad reset button, and resume motor starting.