A5015 alarm in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/A5015 alarm in ABB ACS550 drive

The A5015 alarm in the ABB ACS550 drive indicates that control panel keypad buttons are disabled because the local control mode lock has been activated. The drive inhibits local start, stop, and reference commands from the keypad to prevent unauthorized manual interference with automated supervisory control.

When parameter 1606 LOCAL LOCK is engaged (set to 1 [TRUE] or tied to an active digital input), the drive firmware blocks the LOC/REM key and associated manual run buttons on both the basic and assistant control panels. The internal control state machine strictly enforces remote operation via terminal I/O (EXT1 / EXT2) or fieldbus serial communication. Any attempt to press the local control button or enter manual mode causes the keypad processor to reject the serial keypress interrupt and flash the A5015 notification, ensuring that plant automation loops and process interlocks remain in exclusive control of motor modulation.

What Causes A5015 in ABB ACS550?

  1. Parameter 1606 LOCAL LOCK set to 1 [TRUE], permanently disabling local keypad mode.
  2. Digital input assigned in parameter 1606 receiving an active 24 V DC signal locking local control.
  3. Remote PLC or SCADA supervisory system writing a local lockout command via embedded fieldbus.
  4. Inadvertent activation of parameter locks through security passcodes in parameter 1602 PARAMETER LOCK.
  5. Keypad communication firmware rejecting local mode transitions during active process run sequences.

Step-by-Step Troubleshooting and Solutions

  1. Navigate to parameter 1606 LOCAL LOCK using the control panel navigation keys.
  2. Change the value of parameter 1606 to 0 [NOT SEL] to unlock the keypad buttons.
  3. If parameter 1606 is assigned to a digital input (e.g., DI1 through DI6), inspect terminal voltages using a digital multimeter and de-energize the locking signal.
  4. Verify parameter 1602 PARAMETER LOCK to ensure parameter access is opened with the correct passcode if access to parameter 1606 is restricted.
  5. Press the LOC/REM button on the control panel to confirm that control switches smoothly between REM (Remote) and LOC (Local) modes.

Preventative Maintenance to Avoid A5015 Faults

Document local lockout procedures in facility operating protocols, restrict parameter edit permissions to certified automation engineers, and review digital input assignments during scheduled control audits.

Frequently Asked Questions (FAQs)

What is the meaning of A5015 alarm in ABB ACS550 drive?

The A5015 alarm indicates that the control panel’s local mode pushbuttons are locked out by parameter 1606 to prevent manual override.

What are the primary causes of A5015 alarm?

This alarm occurs when parameter 1606 is enabled, a digital input holding the local lock is energized, or supervisory PLC software restricts local control.

How do I troubleshoot and correct A5015 alarm?

Access parameter 1606 LOCAL LOCK, set its value to NOT SEL or remove the active digital input signal, and press the LOC/REM button to restore manual operation.