The A6B1 alarm occurs when a new user passcode has been entered into the ABB ACS560 drive but has not yet been verified. The drive keeps this alarm active to prevent security lockouts caused by unintentional keystrokes or forgotten codes.
The parameter protection system requires dual-entry confirmation before applying new encryption keys. Until confirmed, the drive firmware isolates parameter write privileges for critical control loops and power electronic settings. This protective state prevents operators from locking out access to vital motor ratings, current limits, or DC braking configurations due to an unconfirmed entry.
What Causes A6B1 in ABB ACS560?
- A technician entered a new security string in parameter
96.100 Change user pass codewithout typing it into confirmation parameter96.101. - The control panel connection dropped or timed out midway through the user password change sequence.
- Typographical mismatch occurred between the entry in
96.100and the subsequent entry in96.101 Confirm user pass code. - Commissioning software disconnected unexpectedly during a bulk security update routine.
Step-by-Step Troubleshooting and Solutions
- Open parameter group
96 Systemand locate parameter96.101 Confirm user pass code. - Type the identical numeric code entered into
96.100into parameter96.101to confirm the new pass code. - To cancel the password update process, close the user lock directly by entering
0or an invalid code in parameter96.02 Pass code. - Verify that parameter
96.102 User lock functionalityretains the desired operational access permissions. - Confirm that alarm code A6B1 is cleared from the control panel notification bar.
Preventative Maintenance to Avoid A6B1 Faults
Conduct password updates strictly through the assistant panel interface or stable PC software connections. Always maintain written records of active drive credentials inside authorized engineering repositories to avoid lost access during commissioning.
Frequently Asked Questions (FAQs)
What is the meaning of A6B1 fault in ABB ACS560 drive?
It warns that a new user passcode was entered into parameter 96.100 but has not yet been verified in parameter 96.101.
What are the primary causes of A6B1 fault?
This alarm is triggered when a user edits the passcode but abandons the verification step or experiences a panel communication timeout.
How do I troubleshoot and correct A6B1 fault?
Enter the matching passcode in parameter 96.101 to finalize the change, or enter an invalid code in parameter 96.02 to abort.