The A985 alarm indicates that external supervisory device 5 has signaled an active fault or warning state in the ABB ACS560 drive. The drive generates this advisory warning to alert operators of external system discrepancies while maintaining running operation.
Through parameter 31.09 External event 5 source, the drive monitors high-level automation handshakes such as PLC supervisory permissives, external motor blower circuit breaker overloads, or ventilation louvre limit switches. When an event signal triggers, parameter 31.10 External event 5 type governs the drive reaction. Continuing to operate with tripped auxiliary equipment (such as an inoperative forced motor cooling fan) can result in severe motor thermal insulation breakdown.
What Causes A985 in ABB ACS560?
- Tripped external device 5 contact (e.g., motor auxiliary cooling blower overload or PLC permissive drop).
- Misassigned input source in parameter
31.09 External event 5 sourcepointing to an open digital pin. - Broken control cable, disconnected terminal block, or loose wire strand on the designated input.
- Incompatible logic assignment in parameter
31.10 External event 5 type. - Intermittent
24V DCauxiliary control loop power dip or loose external relay socket.
Step-by-Step Troubleshooting and Solutions
- Navigate to parameter
31.09 External event 5 sourceto identify the assigned digital terminal or communication bit. - Inspect the external equipment associated with device 5 (e.g., motor forced cooling fan breaker or damper actuator switch).
- Measure voltage across the monitored input terminal and ground using a digital multimeter; confirm
24V DCis present when healthy. - Review parameter
31.10 External event 5 typeto confirm the appropriate response mode is programmed. - Tighten all control terminal screws and ensure shielding is properly grounded to prevent EMI-induced triggering.
Preventative Maintenance to Avoid A985 Faults
Test external auxiliary equipment including blower motor overloads and dampers during routine plant preventive maintenance shutdowns. Verify that control wiring terminals are torqued correctly and audit parameter settings annually using Drive Composer software.
Frequently Asked Questions (FAQs)
What is the meaning of A985 fault in ABB ACS560 drive?
It warns that external monitoring device 5 has detected an abnormal condition or that an external interlock contact has opened.
What are the primary causes of A985 fault?
This alarm is mainly caused by tripped external circuit breakers, loose digital wiring, auxiliary fan overloads, or misconfigured source parameters.
How do I troubleshoot and correct A985 fault?
Check parameter 31.09 to identify the source terminal, inspect the external protection device, test for 24V DC voltage, and reset the field hardware.