The 3381 fault indicates an output phase loss condition where the ABB ACS560 drive detects an open circuit or missing connection across one of the three motor output phases. The drive trips immediately to prevent single-phasing current overstress and motor damage.
Current sensors on inverter output terminals U2, V2, W2 continuously measure instantaneous phase currents. When one phase open-circuits, the motor is subjected to unbalanced single-phase excitation, generating intense negative-sequence magnetic braking torque and massive rotor heating. The inverter control disables PWM gate firing instantaneously to protect the remaining active IGBT half-bridges from extreme thermal overcurrent and prevent intermediate DC link ripple surges.
What Causes 3381 in ABB ACS560?
- Physical disconnection, snapped conductor, or loose terminal screw on motor output terminals
U2, V2, W2. - Open circuit within motor stator windings or disconnected terminal jumpers inside the motor terminal connection box.
- Open contacts or delayed contact closure on an output safety isolator switch or motor contactor.
- Motor nominal current significantly below drive capacity (less than
1/6of drive nominal output current) operating in scalar mode. - Defective internal Hall-effect output current transducer or damaged analog sensing channel on the drive power board.
Step-by-Step Troubleshooting and Solutions
- Isolate power, lock out the drive, and inspect all motor cable connections at drive terminals
U2, V2, W2and the motor terminal box. - Measure winding resistance between motor phases (U-V, V-W, W-U) using a low-resistance digital ohmmeter to confirm phase balance.
- Perform an insulation resistance test at 500V or 1000V DC between each motor lead and earth ground using a calibrated megger.
- Inspect auxiliary output contactors or local maintenance disconnect switches; confirm auxiliary contacts close reliably before run commands.
- If operating a very small motor in scalar mode (less than
1/6drive rating), set parameter31.19 Motor phase lossto[0] No action.
Preventative Maintenance to Avoid 3381 Faults
Check terminal torque on motor connections during scheduled preventive maintenance, inspect flexible motor cabling in drag chains for fatigue fractures, and test auxiliary motor disconnect interlock contacts regularly.
Frequently Asked Questions (FAQs)
What is the meaning of 3381 fault in ABB ACS560 drive?
The 3381 fault indicates that current flow has been interrupted on one of the motor output phases, tripping the drive to avoid single-phasing the motor.
What are the primary causes of 3381 fault?
Primary causes include disconnected motor cables, open stator windings, defective output contactors, and motors drawing current below sensing thresholds in scalar mode.
How do I troubleshoot and correct 3381 fault?
Check terminal connections at U2, V2, W2, measure phase resistance balance, test motor insulation with a megger, and verify parameter 31.19 settings.