5681 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/5681 fault in ABB ACS560 drive

The 5681 fault indicates that serial data transmission errors have been detected between the drive control unit and the power unit in the ABB ACS560. The drive initiates a protective trip to prevent desynchronized pulse generation across the inverter stage.

The drive control unit communicates continuously with the power unit to transmit high-speed PWM firing signals and receive instantaneous phase current and intermediate DC link voltage telemetry. When communication packets suffer CRC check failures, dropped frames, or excessive latency, the control processor cannot safely command the IGBT gate drivers. The drive immediately terminates modulation, protecting power transistors from erratic switching and preventing intermediate DC bus overvoltage surges.

What Causes 5681 in ABB ACS560?

  1. Loose, poorly seated, or mechanically strained internal communication cable connecting the control unit to the power unit.
  2. High-frequency electromagnetic noise radiated from unshielded motor power cables into internal low-voltage harnesses.
  3. Oxidation, pin corrosion, or mechanical damage on internal card-edge or flat ribbon cable connectors.
  4. Voltage ripple or brownout conditions on the internal low-voltage power supply rails powering communication transceivers.
  5. Hardware component degradation or transceiver IC failure on the control card or power unit interface board.

Step-by-Step Troubleshooting and Solutions

  1. Isolate incoming mains AC power, verify DC bus discharge below 50V DC across UDC+ and UDC-, and open the drive casing.
  2. Inspect the internal ribbon cable or connector linking the control unit to the power unit; re-seat both ends firmly.
  3. Examine the cable for physical pinches, sharp bends, or bent connector pins that could impair high-speed data transmission.
  4. Verify that motor power cables at terminals U2, V2, W2 use 360-degree EMC shielding clamps to prevent high-frequency radiation.
  5. Perform a 500V DC megger insulation resistance test across motor phases to rule out capacitive leakage; replace cables or board if fault persists.

Preventative Maintenance to Avoid 5681 Faults

Inspect internal cable harnesses during scheduled servicing, verify that all internal grounding clips remain firmly seated, and install proper motor line filters or shielded cables to prevent high-frequency noise interference.

Frequently Asked Questions (FAQs)

What is the meaning of 5681 fault in ABB ACS560 drive?

The 5681 fault indicates that data transmission errors have occurred between the drive control unit and power unit, tripping the drive to avoid modulation errors.

What are the primary causes of 5681 fault?

Primary causes include loose internal ribbon cables, electromagnetic noise interference from motor cables, damaged connector pins, and faulty transceiver chips.

How do I troubleshoot and correct 5681 fault?

Isolate power, re-seat the internal control-to-power unit ribbon cable, inspect connector pins for damage, verify EMC cable shielding, and power cycle.