6591 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/6591 fault in ABB ACS560 drive

The 6591 fault signals that a communication timeout occurred during an active backup creation or restore sequence on the ABB ACS560 drive. The drive aborts the operation and trips to prevent partial configuration files from corrupting control logic.

During backup restoration, blocks of critical motor control, fieldbus, and I/O parameters are transferred sequentially to internal memory. If serial packet transfer drops midway, the drive enters an indeterminate state where motor nominal currents or protection limits may be unpopulated. To prevent catastrophic motor runaway or inverter bridge short circuits, the processor disables PWM modulation and locks out startup commands until the timeout is cleared.

What Causes 6591 in ABB ACS560?

  1. Premature removal or physical dislodging of the assistant control panel during an ongoing backup or restore cycle.
  2. Loose, unshielded, or disconnected USB-to-RJ45 programming cable when using Drive Composer software.
  3. PC operating system sleep mode, serial port driver timeout, or laptop battery shutdown during transfer.
  4. Corrupted flash memory sector on the control panel preventing block-write acknowledgment signals.
  5. Excessive electromagnetic noise coupling into the keypad extension door-mount cable.

Step-by-Step Troubleshooting and Solutions

  1. Inspect the control panel connection; remove and firmly reseat the keypad into the drive cradle until latched.
  2. If using Drive Composer, verify that the USB cable is intact, securely connected, and not routed alongside high-voltage motor lines.
  3. Verify whether the control panel or PC software is still frozen in an active backup or restore state.
  4. Power cycle the drive control board to clear the serial communications buffer and release the memory lockout.
  5. Re-attempt the backup or restore procedure via Menu > Backups using a known-stable control panel or PC.

Preventative Maintenance to Avoid 6591 Faults

Never unseat the keypad or disconnect PC cables while the drive display shows a progress bar. Use high-quality, shielded USB cables with ferrite beads during field commissioning, and keep door-mounted keypad extension leads away from noisy inverter output conductors.

Frequently Asked Questions (FAQs)

What is the meaning of 6591 fault in ABB ACS560 drive?

It warns that the drive lost communication with the control panel or PC software during an active parameter backup or restore transfer.

What are the primary causes of 6591 fault?

This fault occurs when keypads are removed mid-transfer, USB cables are unplugged, PC tools freeze, or high serial noise corrupts packets.

How do I troubleshoot and correct 6591 fault?

Check the physical keypad seating, verify PC cable integrity, power cycle the drive to clear the transfer state, and retry the operation.