A582 alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/A582 alarm in ABB ACS560 drive

The A582 warning indicates that an auxiliary cooling fan in the ABB ACS560 drive is disconnected, mechanically jammed, or absent. This protective alarm alerts maintenance personnel that forced-air enclosure cooling has degraded, creating risks of elevated thermal stress across internal control circuits.

Auxiliary cooling circuits in larger ACS560 frame sizes circulate air over the internal control board, interface power supplies, and DC link capacitors. The main processor monitors auxiliary fan rotation via tachometer feedback pulses or current sensing across the control board fan headers. When tachometer feedback drops below expected limits, code A582 is asserted. While the primary heatsink blower may still operate, loss of auxiliary airflow elevates enclosure ambient temperatures, degrades capacitor electrolyte lifespan, and can prompt the drive firmware to derate IGBT switching frequencies.

What Causes A582 in ABB ACS560?

  1. Auxiliary cooling fan disconnected or loose from its dedicated header pin on the control unit.
  2. A mechanical obstruction, lint build-up, or foreign object seizing the fan impeller blades.
  3. Auxiliary code 0001 indicating auxiliary fan 1 failure, or auxiliary code 0002 indicating auxiliary fan 2 failure.
  4. The front protective cover is loose, unlatched, or removed during commissioning, defeating the internal air baffle guide.
  5. Internal bearing seizure or electrical coil breakdown within the 24V DC auxiliary fan motor assembly.

Step-by-Step Troubleshooting and Solutions

  1. Review the auxiliary diagnostic sub-code in the drive control panel to isolate whether fan 1 (0001) or fan 2 (0002) is flagged.
  2. Isolate main power, observe the 5-minute DC bus discharge window, and inspect the control board fan connector to ensure it is fully seated.
  3. Spin the auxiliary fan blades manually to check for mechanical resistance, dirt buildup, or broken impeller fins.
  4. Fasten and secure the drive front casing completely, ensuring all retention screws are tightened so internal interlocks and air channels align.
  5. Test for 24V DC supply voltage at the auxiliary fan harness; if voltage is present but rotation fails, replace the fan cartridge.

Preventative Maintenance to Avoid A582 Faults

Clean cabinet ventilation louvers regularly, blow dry compressed air across auxiliary fan blades every quarter, verify front casing tightness during routine inspections, and replace auxiliary cooling fan units before reaching their 40,000-hour operating life.

Frequently Asked Questions (FAQs)

What is the meaning of A582 fault in ABB ACS560 drive?

The A582 warning code indicates that the drive control unit cannot detect proper operation or electrical feedback from an internal auxiliary cooling fan.

What are the primary causes of A582 fault?

Common causes include a disconnected control board fan plug, an impeller jammed with debris, a missing front enclosure cover, or a worn-out fan motor.

How do I troubleshoot and correct A582 fault?

Inspect the specific auxiliary code to locate the fan, verify wire harness connections, clear impeller blockages, reinstall the front cover, or replace the fan.