A6E5 alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/A6E5 alarm in ABB ACS560 drive

The A6E5 warning indicates a configuration conflict between the physical hardware switch setting and the software parameter configuration of an analog input in the ABB ACS560 drive. This protective alarm warns that input signal conditioning does not match incoming reference expectations.

The control unit of the ACS560 incorporates dedicated hardware switches or jumpers alongside software parameters to configure analog inputs AI1 and AI2 for either voltage mode (0 to 10V) or current mode (0/4 to 20mA). When the digital signal processor evaluates the signal scaling in parameter 12.15 AI1 unit selection or 12.25 AI2 unit selection against hardware sensor state feedback and detects a mismatch, alarm A6E5 triggers. Running current loop signals into an input set for voltage creates high voltage drops across terminal resistors, whereas feeding a 10V potential into a low-impedance current shunt causes excessive thermal dissipation across the input filtering circuit.

What Causes A6E5 in ABB ACS560?

  1. The analog input DIP switch or jumper is toggled to current mode (mA) while parameter 12.15 is programmed for voltage (V).
  2. The analog input hardware is switched to voltage mode (V) while parameter 12.25 is set for current (mA).
  3. A technician adjusted the physical terminal block switches without performing a necessary control unit reboot.
  4. Corrupted analog scaling parameters stored in group 12 Standard AI following a partial parameter restore.
  5. Damaged input sensing circuits or broken selector switch contacts on the ACS560 control card.

Step-by-Step Troubleshooting and Solutions

  1. Review the auxiliary diagnostic code in the active event log to identify whether AI1 or AI2 is the source of the conflict.
  2. Inspect the physical hardware slide switch located near the control board terminal strip to verify its exact physical position (V or mA).
  3. Align software parameters in parameter group 12, matching parameter 12.15 (for AI1) or 12.25 (for AI2) to the physical switch setting.
  4. Reboot the drive control board to latch the hardware switch setting by executing parameter 96.08 Control board boot or performing a complete power cycle.
  5. Measure incoming analog signals with a calibrated digital multimeter across terminals AI1/AI2 and AGND to ensure signal amplitude matches the selected mode.

Preventative Maintenance to Avoid A6E5 Faults

Document control wiring schematics with designated signal types prior to installation, lock enclosure doors against unauthorized switch tampering, and verify that both parameter definitions and hardware jumper positions match after updating firmware.

Frequently Asked Questions (FAQs)

What is the meaning of A6E5 fault in ABB ACS560 drive?

The A6E5 code is a parametrization warning indicating a discrepancy between the physical hardware jumper setting and the software parameters of an analog input.

What are the primary causes of A6E5 fault?

It is caused by mismatched voltage/current DIP switches, incorrect values in parameter 12.15 or 12.25, or failure to reboot the control board after modifying hardware switches.

How do I troubleshoot and correct A6E5 fault?

Check the event log auxiliary code, match parameter 12.15 or 12.25 to the physical switch, and execute parameter 96.08 to reboot the control unit.