A6E6 alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/A6E6 alarm in ABB ACS560 drive

The A6E6 warning indicates an invalid configuration within the User Load Curve (ULC) parameter structure of the ABB ACS560 drive. This diagnostic alarm alerts users that envelope limit points violate mathematical continuity, disabling process supervision functions.

The User Load Curve feature monitors mechanical torque as a function of shaft speed or output frequency, protecting driven equipment like conveyors, crushers, and pumps against broken belts or mechanical stalls. The system constructs an operating envelope defined by five consecutive coordinate pairs. When parameter validation routines evaluate group 37 User load curve and detect non-monotonic speed points or an underload curve programmed higher than an overload curve, code A6E6 flags. The drive continues inverter modulation but suspends ULC supervision to avoid erroneous overtorque or undertorque trips.

What Causes A6E6 in ABB ACS560?

  1. Auxiliary code 0000: Speed coordinates in parameters 37.11 through 37.15 are inconsistent and do not increase monotonically.
  2. Auxiliary code 0001: Frequency coordinates in parameters 37.16 through 37.20 are out of ascending numerical sequence.
  3. Auxiliary code 0002: An underload limit point in parameters 37.21 through 37.25 is set higher than its corresponding overload point in parameters 37.31 through 37.35.
  4. Auxiliary code 0003: An overload threshold value is configured lower than the matching underload baseline value.
  5. Inadvertent manual data entry during commissioning causing curve limits to intersect or cross over each other.

Step-by-Step Troubleshooting and Solutions

  1. Check the active auxiliary sub-code on the control panel to pinpoint the exact group of misconfigured coordinate parameters.
  2. If auxiliary code is 0000 or 0001, verify that each successive coordinate point has a strictly higher value than the preceding one (e.g., 37.11 < 37.12 < 37.13 < 37.14 < 37.15).
  3. If auxiliary code is 0002 or 0003, compare underload parameters (37.21 to 37.25) directly with overload parameters (37.31 to 37.35) at each speed point.
  4. Adjust parameter values so that each overload point maintains an adequate margin of at least 10% to 15% above its corresponding underload baseline.
  5. Cycle parameter 37.01 ULC function from active to disabled and back to reinitialize envelope calculation math.

Preventative Maintenance to Avoid A6E6 Faults

Plot load profile coordinates on paper or spreadsheet software before commissioning parameter group 37, back up operational configurations using the assistant keypad, and lock engineering parameter groups against unauthorized field modification.

Frequently Asked Questions (FAQs)

What is the meaning of A6E6 fault in ABB ACS560 drive?

The A6E6 alarm warns that coordinates defining the User Load Curve feature have invalid mathematical progression or intersecting limits.

What are the primary causes of A6E6 fault?

This warning is triggered by descending speed or frequency points, or by programming underload curve thresholds higher than overload thresholds.

How do I troubleshoot and correct A6E6 fault?

Check the auxiliary code, ensure all speed and frequency steps ascend in value, and verify that overload parameters exceed underload settings at all points.