The A791 alarm indicates that the external dynamic brake resistor is broken, open-circuited, or disconnected from the drive. The ABB ACS560 issues this pre-warning when the brake chopper diagnostic circuit detects an open loop across braking terminals.
During motor deceleration or regenerative braking cycles, the motor acts as an induction generator, feeding kinetic energy back through the inverter into the intermediate DC circuit. When the DC bus voltage rises toward overvoltage limits, the internal brake chopper IGBT turns on to dump excess energy into an external dynamic braking resistor connected across terminals R+ and R-. If the resistor element is cracked or disconnected, the chopper cannot dissipate regeneration current. The drive flags A791 to alert operators before the DC link trips on destructive overvoltage.
What Causes A791 in ABB ACS560?
- Brake resistor physically disconnected or not installed while the brake chopper function is enabled in parameter group
43 Brake chopper. - Burned out, fractured, or open-circuit resistor wire wound elements inside the braking enclosure.
- Tripped external thermal overload switch wired in series with the brake resistor circuit.
- Loose, corroded, or disconnected conductor terminations on drive terminals
R+andR-. - Blown semiconductor fast-acting fuse protecting the external braking resistor branch.
Step-by-Step Troubleshooting and Solutions
- Inspect Resistor Physical Connections: Verify that external braking resistor leads are securely clamped into drive terminals
R+andR-(orUDC+andR-depending on frame size). - Measure Cold Resistor Resistance: Disconnect the resistor from the drive, allow it to cool, and measure ohmic resistance using a calibrated multimeter; compare against parameter
43.10 Brake resistor resistance. - Inspect Integrated Thermal Switch: Check whether the thermal bi-metal klixon switch embedded in the resistor grid has tripped open due to past overheating.
- Disable Chopper if Unused: If the application does not use dynamic braking resistors, disable brake chopper operation in parameter group
43 Brake chopperto extinguish nuisance warnings. - Inspect Chopper Fuses: Check internal or inline semiconductor branch fuses protecting the dynamic braking module for open-circuit continuity.
Preventative Maintenance to Avoid A791 Faults
Inspect dynamic braking resistor grids semiannually for signs of ceramic cracking, heat discoloration, or structural warping. Clean ambient dust off ventilation louvers to prevent localized heat pockets that weaken wire wound resistance elements over time.
Frequently Asked Questions (FAQs)
What is the meaning of A791 fault in ABB ACS560 drive?
The A791 alarm indicates that the dynamic braking resistor circuit is open, missing, or broken while the brake chopper is active.
What are the primary causes of A791 fault?
This alarm is mainly caused by open-circuit resistor elements, loose connections on terminals R+ and R-, tripped thermal overload switches, or parameter mismatches.
How do I troubleshoot and correct A791 fault?
Measure the ohmic resistance of the resistor with a multimeter, verify secure wiring on braking terminals, and disable the chopper in group 43 if unneeded.