A8A2 alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/A8A2 alarm in ABB ACS560 drive

The A8A2 warning indicates that a relay output on the ABB ACS560 drive is switching states at an excessively rapid frequency. This rate-of-change alarm warns that severe mechanical contact chatter will destroy relay contacts prematurely if signal routing is not corrected.

Electromechanical relays on the ACS560 control card are designed for slow-to-moderate status indication (such as drive running, fault status, or ready state). If a user erroneously configures a relay source parameter in group 10 Standard DO, RO to monitor a high-frequency pulsating parameter (e.g., motor output frequency ripple, current limit hunting, or an unfiltered comparator signal), the relay armature chatters rapidly. Repetitive micro-arcing across contacts generates localized heat, pits the conductive plating, and risks rapid contact welding. Warning A8A2 alerts operators to intervene before thermal arcing damages the control board substrate.

What Causes A8A2 in ABB ACS560?

  1. Relay output source parameter 10.24 RO1 source, 10.27 RO2 source, or 10.30 RO3 source mapped to an oscillating or rapid-cycling variable.
  2. Unstable limit comparator thresholds configured in parameter group 32 Supervision lacking sufficient hysteresis filtering.
  3. Severe electrical noise or induced ground interference oscillating digital reference bits within the control logic.
  4. Process hunting conditions causing a motor speed or torque flag to toggle on and off multiple times per second.
  5. Excessive contact chatter driven by noisy external mechanical limit switches tied into relay logic.

Step-by-Step Troubleshooting and Solutions

  1. Examine parameters 10.24, 10.27, and 10.30 to determine which relay output is mapped to an unstable switching signal source.
  2. Remap the relay source to a stable, slow-changing binary indicator, such as Ready run, Running, or Fault (-1).
  3. If monitoring threshold variables, introduce hysteresis band filtering or off-delay timers in parameter group 32 Supervision to dampen rapid toggling.
  4. Program an on-delay or off-delay timer in parameters 10.25 RO1 ON delay and 10.26 RO1 OFF delay (minimum 1.0s to 2.0s) to buffer relay actions.
  5. For applications requiring high-frequency pulsing or tachometer replication, redirect the signal to a solid-state transistor output or fieldbus register.

Preventative Maintenance to Avoid A8A2 Faults

Never configure electromechanical relays to track dynamic analog thresholds without on/off delay filters, use transistor digital outputs for rapid pulsed feedback, and review parameter event logs during machine commissioning to eliminate chatter.

Frequently Asked Questions (FAQs)

What is the meaning of A8A2 fault in ABB ACS560 drive?

The A8A2 warning alerts users that an onboard electromechanical relay is toggling on and off faster than its mechanical design parameters allow.

What are the primary causes of A8A2 fault?

It is caused by mapping relay outputs to dynamic process variables, fluctuating threshold comparisons, or lacking proper on/off delay hysteresis.

How do I troubleshoot and correct A8A2 fault?

Reconfigure relay source parameters in group 10 to stable status flags, program on/off delays in parameters 10.25 and 10.26, or use transistor outputs.