The A991 warning indicates an invalid chronological sequence within the seasonal calendar configuration tied to motor thermal or timed functions in the ABB ACS560 drive. This system alarm alerts operators that a season start date has been programmed prior to the preceding season’s start date.
In the ACS560 control architecture, timed scheduling and thermal derating profiles use calendar-based transitions governed by parameter group 34 Timed functions. When internal clock services calculate operational transitions, all seasonal boundary timestamps must ascend sequentially throughout the calendar year. Programming an out-of-order date causes an overlapping calendar exception in the internal scheduler. While the inverter continues active pulse-width modulation without dropping the motor output, automatic seasonal speed adjustments, cooling overrides, and associated thermal monitoring functions are halted until date logic is reconciled.
What Causes A991 in ABB ACS560?
- A seasonal transition date in parameters
34.60through34.63is configured to start before the previous season. - Inadvertent manual entry of calendar day and month values into parameter
34.61 Season 2 start date. - The real-time clock (RTC) on the assistant control panel is set to an incorrect base year or uninitialized date.
- A parameter restore from another drive unit that had conflicting daylight saving or seasonal calendar structures.
- Incomplete setup of parameter group
34 Timed functionswhere only partial seasonal dates were populated.
Step-by-Step Troubleshooting and Solutions
- Access parameter group
34 Timed functionsvia the control panel and review parameters34.60 Season 1 start datethrough34.63 Season 4 start date. - Reconfigure all seasonal dates in strictly ascending calendar order (e.g., Season 1 starting in January/Spring, followed sequentially by Seasons 2, 3, and 4).
- Verify the real-time clock settings in parameter group
96 System, ensuring current time, date, and daylight saving rules are accurate. - If seasonal profiles are not utilized by the application, disable the seasonal timer function within parameter
34.10 Timed functions enable. - Reboot the drive control board using parameter
96.08 Control board bootor execute a complete power cycle to clear the active warning.
Preventative Maintenance to Avoid A991 Faults
Map scheduled operational calendar changes in documentation before entering them into parameter group 34, ensure control panel backup batteries maintain clock integrity during outages, and audit timer schedules annually.
Frequently Asked Questions (FAQs)
What is the meaning of A991 fault in ABB ACS560 drive?
The A991 code is a configuration warning indicating that season transition start dates in the timer settings violate chronological calendar sequence.
What are the primary causes of A991 fault?
It is caused by setting a season start date earlier than the preceding season, entering inverted date coordinates, or restoring unmatched calendar files.
How do I troubleshoot and correct A991 fault?
Open parameter group 34, reconfigure parameters 34.60 through 34.63 in ascending date order, verify the system clock, and reboot the control board.