AFAA alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/AFAA alarm in ABB ACS560 drive

The AFAA warning is an informational status notice indicating that the ABB ACS560 drive is executing an automatic fault reset sequence. This protective warning notifies operators that a tripped state is being automatically cleared according to programmed recovery rules.

The ACS560 integrates an automated fault recovery engine configured in parameter group 31 Fault functions. When transient events such as momentary supply undervoltage, minor overcurrent spikes, or loss of analog reference trip the drive, parameter 31.12 Autoreset selection initiates a countdown timer before resetting the trip latch. Warning AFAA displays on the control panel during this delay window. The intermediate DC link capacitors remain energized while the internal gate pulses are suppressed. Once the reset timer in parameter 31.14 Number of trials expires successfully, the drive re-engages motor modulation without requiring manual operator intervention.

What Causes AFAA in ABB ACS560?

  1. An active drive trip condition occurred that matches an enabled automatic reset function in parameter 31.12 Autoreset selection.
  2. The drive is holding modulation during the delay period defined in parameter 31.13 Autoreset delay before clearing the fault.
  3. Transient electrical disturbances on incoming supply phases L1, L2, L3 triggering repetitive self-clearing undervoltage trips.
  4. Transient mechanical shock loads briefly triggering overcurrent conditions configured for automatic reset.
  5. Intermittent 4 to 20mA analog signal dropouts triggering auto-recovering reference loss routines.

Step-by-Step Troubleshooting and Solutions

  1. Inspect the drive event log history to identify the primary fault code that triggered the initial autoreset sequence.
  2. Review parameter 31.12 Autoreset selection to audit which fault categories (overcurrent, undervoltage, analog input) are enabled for auto-recovery.
  3. Examine parameters 31.14 Number of trials and 31.15 Trial time to verify that the drive is not repeatedly attempting to clear persistent hardware faults.
  4. Check incoming AC line stability using a power quality logger to eliminate recurring grid voltage dips or phase sags.
  5. If automatic restarting poses mechanical safety risks to equipment or personnel, disable the function in parameter 31.12.

Preventative Maintenance to Avoid AFAA Faults

Inspect upstream electrical distribution breakers to ensure stable voltage delivery, verify wiring tightness on analog transducer terminals, and ensure automatic restarting sequences conform to machine safety standards.

Frequently Asked Questions (FAQs)

What is the meaning of AFAA fault in ABB ACS560 drive?

The AFAA code is an informational warning indicating that the drive is currently executing an automated fault reset and restart sequence.

What are the primary causes of AFAA fault?

It occurs when an auto-resettable fault trips the inverter, initiating the programmed autoreset timer configured in parameter group 31.

How do I troubleshoot and correct AFAA fault?

Examine the event log to identify and resolve the underlying primary trip, and adjust autoreset trial parameters in parameter group 31 if needed.