AFF5 alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/AFF5 alarm in ABB ACS560 drive

The AFF5 alarm indicates that the Safe Torque Off (STO) safety function was active and has been reset while the drive was operating in Override mode. The ABB ACS560 halts operation and requires a new rising-edge start command to re-energize the motor.

Override mode (parameter group 70 Override) is engineered for critical life-safety and emergency infrastructure, such as tunnel smoke-extraction or stairwell pressurization fans, where the drive ignores non-critical faults to maintain ventilation. However, if the hardware Safe Torque Off inputs across terminals IN1, IN2 and +24V are interrupted, the drive hardware immediately de-energizes the gate drivers of the inverter IGBTs, disabling torque generation. When the STO circuit is subsequently restored, safety standards require that the drive does not restart automatically. The drive issues AFF5 to enforce anti-restart protection until the control logic detects an explicit new start command cycle.

What Causes AFF5 in ABB ACS560?

  1. Safe Torque Off (STO) circuit cycled or tripped open while the drive was operating in Override mode.
  2. Loose, broken, or intermittent wiring connections on STO terminals IN1, IN2, or SGND.
  3. Emergency stop safety relay or safety PLC resetting STO channels while an active start command remains held high.
  4. False noise tripping on STO input circuits due to unshielded control wiring routed alongside motor power leads.
  5. Failure to toggle the start command input following the clearing of an emergency safety event.

Step-by-Step Troubleshooting and Solutions

  1. Verify Safe Torque Off Hardware: Use a multimeter to measure voltage on terminals IN1 and IN2 with respect to SGND; ensure both channels receive a steady, simultaneous 24V DC.
  2. Cycle the Start Signal: Remove the active start signal (switch the assigned digital input from high to low, or toggle fieldbus start bit), then reapply the start command to establish a clean rising edge.
  3. Inspect Parameter Group 70: Review parameter group 70 Override to confirm whether Override mode is actively commanded and that the override start source is healthy.
  4. Check Emergency Relay Latches: Ensure that upstream safety controllers, light curtains, or E-stop relays have completely reset and are not chattering.
  5. Inspect STO Wiring Integrity: Tighten terminal clamp screws on the STO connector block and verify that shielded cables are properly grounded at the drive frame clamp.

Preventative Maintenance to Avoid AFF5 Faults

Periodically test dual-channel STO operation during planned plant outages to ensure both safety channels switch simultaneously within 200 ms. Ensure Override mode settings are audited annually in compliance with local fire safety and life-safety building codes.

Frequently Asked Questions (FAQs)

What is the meaning of AFF5 fault in ABB ACS560 drive?

The AFF5 alarm indicates that the Safe Torque Off circuit was tripped and restored during Override mode, requiring a fresh start command before resuming motor operation.

What are the primary causes of AFF5 fault?

This alarm occurs when STO inputs are interrupted while Override mode is engaged, followed by safety reset without cycling the operational start command.

How do I troubleshoot and correct AFF5 fault?

Verify that 24V DC is restored across STO terminals IN1 and IN2, remove and reapply the drive start command signal, and confirm override parameter settings.