2340 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/2340 fault in ABB ACS560 drive

The 2340 fault indicates that the ABB ACS560 drive has detected a direct low-impedance phase-to-phase short-circuit in the motor or motor cabling. High-speed desaturation hardware shuts down gating pulses instantly to prevent catastrophic failure of the inverter IGBTs.

When a phase-to-phase short occurs between output terminals U2, V2, W2, current rises at an extreme rate (di/dt). The drive IGBT gate drivers incorporate desaturation monitoring that detects the collector-emitter voltage (Vce) rising out of saturation during conduction. When aux code 0x0080 is present, it confirms that phase state feedback does not match command signals, indicating a shorted circuit. The gate driver shuts down output pulses within microseconds. Because high fault energy dumps across the freewheeling diodes, attempting repeated starts into a hard short circuit will puncture the IGBT silicon substrate and damage the intermediate DC bus.

What Causes 2340 in ABB ACS560?

  1. Phase-to-phase short circuit within the motor power cables due to mechanical severance, crushing, or heat damage.
  2. Direct dielectric puncture between phase coils in the motor stator windings.
  3. Incorrect motor terminal star/delta bridge link configuration or loose copper strands bridging adjacent terminal studs.
  4. Power factor correction capacitors or surge suppression varistors connected to output terminals U2, V2, W2.
  5. Blown or shorted IGBT semiconductor module or defective gate driver circuit inside the ACS560 drive.

Step-by-Step Troubleshooting and Solutions

  1. Isolate the drive, wait 5 minutes for the DC bus capacitors to discharge below 5V DC, and verify zero voltage across UDC+ and UDC-.
  2. Disconnect motor cables from terminals U2, V2, W2 and inspect the terminal strip for loose strands or foreign conductive debris.
  3. Measure phase-to-phase resistance across cable leads U-V, V-W, and W-U using a digital micro-ohmmeter to identify direct short circuits.
  4. Conduct a phase-to-phase insulation test with a megger at 500V DC between phases; verify balanced resistance exceeding 100 MΩ.
  5. Perform a multimeter diode test across internal IGBTs from UDC+ and UDC- to each output terminal U2, V2, W2 (normal diode forward voltage is 0.3V to 0.7V).

Preventative Maintenance to Avoid 2340 Faults

Route motor cables in dedicated grounded metallic conduit away from sharp mechanical edges, verify correct torque on terminal connections, never use power factor capacitors on inverter outputs, and perform routine winding surge testing.

Frequently Asked Questions (FAQs)

What is the meaning of 2340 fault in ABB ACS560 drive?

The 2340 code is a critical short-circuit trip indicating a phase-to-phase short across the motor terminals, cabling, or inverter IGBT module.

What are the primary causes of 2340 fault?

This trip is caused by inter-phase cable shorts, motor stator insulation puncture, wiring bridge errors, or shorted inverter IGBT switches.

How do I troubleshoot and correct 2340 fault?

Disconnect motor cables, check phase-to-phase resistance with a micro-ohmmeter, megger test phase insulation, and perform diode checks on the drive power bridge.