2392 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/2392 fault in ABB ACS560 drive

The 2392 fault indicates that the total earth leakage current of the basic inverter power unit modules has exceeded safe design thresholds. The ABB ACS560 trips instantly to protect power electronics from ground loop overcurrents.

During normal inverter operation, the vector sum of instantaneous output currents flowing through phases U2, V2, W2 should mathematically equal zero ($I_u + I_v + I_w = 0$). Internal summation current transformers continuously track residual current to chassis ground. If capacitive leakage to earth or direct dielectric insulation failure causes this residual current vector to cross protective trip limits, the drive triggers 2392. Operating an inverter with severe earth leakage risks destructive arcing, high ground potential shifts, and flashover damage to the intermediate DC bus.

What Causes 2392 in ABB ACS560?

  1. Power factor correction capacitor banks or transient surge arrestors erroneously connected across motor output terminals.
  2. Degraded, pinched, or water-submerged motor power cabling between the drive and the motor terminal box.
  3. Excessively long motor cable runs generating high parasitic capacitive charging currents to earth.
  4. Moisture condensation, chemical contamination, or carbon tracking inside the motor stator windings.
  5. Defective ground leakage sensing transformers or corrupted current measurement circuits on the drive power unit.

Step-by-Step Troubleshooting and Solutions

  1. Disconnect Output Surge Devices: Verify that no power factor correction capacitors, LC filters, or transient voltage suppressors are wired downstream of terminals U2, V2, W2; remove them immediately.
  2. Perform 1000V DC Megger Test: Disconnect motor leads from the drive and use a 1000V DC megohmmeter to measure insulation resistance phase-to-ground for both the cable and motor; ensure resistance exceeds 10 MΩ.
  3. Check Cable Length Specifications: Confirm that the total motor cable length does not exceed maximum manufacturer guidelines (typically 100 m to 150 m); install an ABB output du/dt filter if long cable runs are unavoidable.
  4. Inspect Motor Terminal Box: Open the motor junction box and inspect for moisture pooling, cracked terminal blocks, or loose grounding bonding conductors.
  5. Test Drive Unconnected: Run the drive in scalar mode with the motor cable completely disconnected; if the 2392 fault trips with no load connected, replace the internal current sensing module.

Preventative Maintenance to Avoid 2392 Faults

Conduct annual insulation resistance logging on all motor feeders to detect gradual insulation degradation before dead ground shorts occur. Ensure drive output motor leads utilize symmetrical shielded cables with continuous 360-degree ground clamps at the drive gland plate.

Frequently Asked Questions (FAQs)

What is the meaning of 2392 fault in ABB ACS560 drive?

The 2392 fault indicates that the drive has detected excessive earth leakage or ground fault current in the inverter power stage or motor circuit.

What are the primary causes of 2392 fault?

This trip is caused by motor winding breakdown, grounded output cables, excessive cable capacitance on long runs, or power factor capacitors connected on the load side.

How do I troubleshoot and correct 2392 fault?

Remove any output capacitors, test motor and cable insulation using a 1000V DC megohmmeter, verify cable length limits, and dry out wet motor terminal boxes.