5081 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/5081 fault in ABB ACS560 drive

The 5081 fault indicates that an auxiliary cooling fan in the ABB ACS560 drive is disconnected, mechanically jammed, or defective. This hardware trip disables drive operation to protect internal control electronics and bus capacitors from overheating.

In mid-to-large ACS560 frame sizes, auxiliary fans circulate air internally across the control board, gate driver cards, and intermediate DC link electrolytic capacitor banks. The control processor monitors auxiliary fan rotational pulses via dedicated circuit headers on the control unit. If tachometer feedback drops out while the auxiliary fan is energized, the drive asserts fault 5081. Operating without active auxiliary airflow leads to thermal hotspot formation on the control PCB, premature degradation of DC bus capacitor dielectric foil, and potential gate driver drift, prompting the drive to lock out modulation.

What Causes 5081 in ABB ACS560?

  1. Auxiliary code 0001: Auxiliary cooling fan 1 is disconnected, stuck, or electrically open.
  2. Auxiliary code 0002: Auxiliary cooling fan 2 is disconnected, stuck, or electrically open.
  3. Mechanical contamination, dust accumulation, or foreign debris preventing the auxiliary fan blades from rotating.
  4. The multi-pin auxiliary fan plug has loosened from its mating connector on the drive control board.
  5. Worn-out fan motor sleeve bearings or open-circuit motor coils within the auxiliary blower housing.

Step-by-Step Troubleshooting and Solutions

  1. Check the active auxiliary sub-code in the control panel event log to identify whether auxiliary fan 1 (0001) or auxiliary fan 2 (0002) failed.
  2. Isolate incoming mains supply, allow the internal DC bus to discharge below 5V DC, and remove the protective casing to access the auxiliary fan assembly.
  3. Check the auxiliary fan harness connection to verify that the connector plug is firmly locked into the control board header.
  4. Inspect the fan blades and rotate them by hand to ensure they spin freely without mechanical binding or grit buildup.
  5. Disconnect the fan plug and test the auxiliary fan using an external 24V DC power supply; if the fan does not spin or draws excessive current, install a replacement unit.

Preventative Maintenance to Avoid 5081 Faults

Keep electrical cabinet filters clean, vacuum internal enclosure dust during annual preventative maintenance shutdowns, ensure proper front cover retention screw torque, and replace auxiliary fans every 3 to 5 years based on operating runtime.

Frequently Asked Questions (FAQs)

What is the meaning of 5081 fault in ABB ACS560 drive?

The 5081 code is an auxiliary fan failure trip indicating that an internal cooling fan on the control card or capacitor bank has stopped operating.

What are the primary causes of 5081 fault?

It is caused by seized fan blades, loose control board wiring harnesses, failed fan motor bearings, or broken auxiliary blower coils.

How do I troubleshoot and correct 5081 fault?

Identify the failed fan via auxiliary sub-codes 0001 or 0002, check wire connections, clear impeller debris, test with 24V DC, and replace the fan if required.