Allen-Bradley Kinetix 350 Servo Drive Fault Codes & Diagnostic Guide
Complete fault code directory, 4-character alphanumeric LED errors, CIP Motion axis exception handling, and step-by-step troubleshooting procedures for the Allen-Bradley Kinetix 350 (Bulletin 2097) servo drive series.
Power Range
0.4 – 3.0 kW (0.5 – 4.0 HP)
Supply Voltage
120V (1-Ph), 240V (1/3-Ph), 480V (3-Ph) AC
Control Modes
Position, Velocity & Torque (CIP Motion)
Operator Interface
4-Character Status Display / Studio 5000
Complete Allen-Bradley Kinetix 350 Fault Code Directory
Use the search box in the table below to quickly find your fault code or exception (e.g., type E04, E18, E45, Overcurrent, or Feedback).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| S 01 Axis enable input | Cause: Axis Enable Input is not active. Remedy:
|
| S 02 Motor not configured | Cause: Faulty intelligent encoder or incorrect motor file. Remedy:
|
| S 03 Feedback not configured | Cause: The associated feedback device has not been configured for use or the configuration does not match what is connected. Remedy:
|
| Sc05 Safe torque off | Cause: The safety function has disabled the power structure. Remedy:
|
| F 02 Illegal Hall State | Cause: Improper connections. Remedy:
|
| F 03 Motor Overspeed | Cause: Motor speed has exceeded 125% of maximum rated speed. Remedy:
|
| F 05 Motor Overtemperature | Cause: High motor ambient temperature and/or Excessive Current. Remedy:
|
| F 07 Motor Thermal Protection | Cause: The machine duty cycle requires an RMS current that exceeds the continuous rating of the motor. Remedy:
|
| F 10 Inverter Overcurrent | Cause: - Motor cables shorted. - Motor winding shorted internally. - Drive temperature too high. - Loss of TTL signal. Remedy:
|
| F 11 Inverter Overtemperature | Cause: Drive fan failed, High cabinet ambient temperature, or Blocked airflow. Remedy:
|
| F 13 Inverter Thermal Protection | Cause: Machine duty cycle exceeds continuous rating OR Motor brake on. Remedy:
|
| F 33 Bus Undervoltage | Cause: DC bus voltage is below limits (460V system < 275V, 230V system < 137V, 120V system < 80V). Remedy:
|
| F 35 Bus Overvoltage | Cause: Excessive regeneration of power, external mechanical power source, or high AC line voltage. Remedy:
|
| F 43 Feedback Loss | Cause: The motor feedback wiring is open, shorted, or missing; OR Excessive noise on feedback signals. Remedy:
|
| F 45 Feedback Serial Comms | Cause: Communication was not established with an intelligent encoder. Remedy:
|
| F 47 Feedback Self Test | Cause: Damage to feedback device. Remedy:
|
| F 50 Hardware Overtravel - Positive | Cause: Dedicated overtravel input is inactive. Remedy:
|
| F 51 Hardware Overtravel - Negative | Cause: Dedicated overtravel input is inactive. Remedy:
|
| F 54 Excessive Position Error | Cause: Partial loss of feedback signals, Improperly sized drive/motor, or Mechanical system out of specifications. Remedy:
|
| F 55 Excessive Velocity Error | Cause:
Remedy:
|
| F 56 Overtorque Limit | Cause:
Remedy:
|
| F 57 Undertorque Limit | Cause:
Remedy:
|
| F 61 Drive Enable Input | Cause:
Remedy:
|
| F 62 Controller Initiated Exception | Cause: User configured software overtravel. Remedy:
|
| Fc 02 Motor Voltage Mismatch | Cause: Wrong motor has been connected to drive. Remedy: Connect appropriate motor to drive. |
| Fc 05 Motor Encoder Battery Loss | Cause: Weak battery or poor battery connection. Remedy:
|
| Fc 06 Motor Encoder Battery Low | Cause: The battery voltage on a battery-backed motor encoder is low enough such that a power loss causes the absolute position to be lost. Remedy: (See Fc 05: Replace battery / Check connection). |
| Fc 14 Excessive Current Feedback Offset | Cause: Current in one or more phases have been lost or remains below a preset level. Remedy: Replace the drive. |
| Fc 26 Runtime Drive Error | Cause: The drive firmware encountered an unrecoverable runtime error. Remedy:
|
| Ic 01 Boot Block Check Sum Fault | Cause: Faulty intelligent encoder. Remedy:
|
| Ic 02 Motor Data Range Error | Cause: Faulty intelligent encoder or incorrect motor file. Remedy:
|
| Ic 03 Motor Feedback Communication Startup | Cause:
Remedy:
|
| Ic 06 Motor Absolute Startup Speed | Cause: Mechanical movement of the machine has caused excessive rotation of the motor during powerup (>100 rpm). Remedy: Allow machine motion to stop before powerup. |
| L001 Identity block corrupted | Cause: Unrecoverable error while starting the drive. Remedy: Reload the firmware and restart the drive. If message repeats, contact Rockwell Automation technical support. |
| L002 Firmware file load failed | Cause: Unrecoverable error while starting the drive. Remedy: Reload the firmware and restart the drive. If message repeats, contact Rockwell Automation technical support. |
| L004 Firmware not programmed (drive is new) | Cause: Drive is new or memory wiped. Remedy: Reload the firmware and restart the drive. |
| L008 DSP load operation failed | Cause: Unrecoverable error while starting the drive. Remedy: Reload the firmware and restart the drive. If message repeats, contact Rockwell Automation technical support. |
| P001 - P007 POST (Power-on Self Test) Failure | Cause:
Remedy: Unrecoverable error during POST. Contact Rockwell Automation technical support to return the drive for repair. |
| nF 01 Control Update Fault | Cause:
Remedy:
|
| nF 02 Processor Watchdog Fault | Cause: The watchdog-circuit monitoring processor operation detected a problem. Remedy:
|
| nF 03 Hardware Fault | Cause:
Remedy:
|
| nF 04 Data Format Error | Cause: Faulty memory component (Data format error discovered in controller-to-drive message). Remedy:
|
How to Clear & Reset Kinetix 350 Servo Drive Faults
- Motion Axis Fault Reset (MAFR): In your Logix controller ladder logic program, trigger an execution pulse on the
MAFRinstruction mapped to the faulted Kinetix 350 CIP Motion axis. - Studio 5000 Motion Direct Commands (MDC): Open the motion axis configuration window in Studio 5000 Logix Designer, right-click the axis, select Motion Direct Commands, choose Reset, and execute the command.
- Safe Torque Off (STO) Reset: If an STO safety interlock tripped (displayed as
S t Oor axis inhibited), restore the safety dual-channel +24V DC circuit into terminal block IOD, verify safety integrity, and issue a Motion Servo On (MSO) command. - Controller / HMI Reset Tag: Program an operator reset pushbutton on your FactoryTalk View or PanelView HMI that sets a bit monitored by your Logix controller to initiate an axis fault clearing routine.
- Control & Mains Power Cycle: Remove both the incoming AC line power (Mains) and the auxiliary 24V DC logic control power. Wait at least 5 minutes for the DC bus capacitors to discharge below 50VDC before restoring power.
⚠️ High-Voltage Electrical Safety Warning:
Dangerous residual DC bus voltages remain energized inside the Kinetix 350 power circuit after AC mains isolation. Always verify with a calibrated digital multimeter across the DC bus terminals [DC+] and [DC-] that the voltage measures strictly below 50VDC before inspecting servo motor power cables (U, V, W), encoder feedback wiring, or external shunt resistors.