Allen-Bradley Kinetix 5500 Servo Drive Fault Codes & Diagnostic Guide
Complete fault code directory, 4-character scrolling LED status messages, CIP Motion exception handling, and diagnostic troubleshooting procedures for the Allen-Bradley Kinetix 5500 (Bulletin 2198) servo drive series.
Power Range
0.2 – 14.6 kW (0.3 – 20 HP)
Supply Voltage
195–528V AC (1-Ph / 3-Ph)
Control Modes
CIP Motion (Position, Velocity, Torque)
Operator Interface
Status Display Keypad / Studio 5000
Complete Allen-Bradley Kinetix 5500 Fault Code Directory
Use the search box in the table below to quickly find your fault code or exception (e.g., type FLT S03, FLT M02, Overcurrent, or Safe Torque Off).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| FLT S03 – MTR OVERSPEED FL Motor Overspeed Factory Limit Fault | Cause: Motor speed has exceeded 125% of its maximum speed. Remedy:
|
| FLT S04 – MTR OVERSPEED UL Motor Overspeed User Limit Fault | Cause: Motor speed has exceeded motor overspeed user limit. Remedy:
|
| FLT S05 – MTR OVERTEMP FL Motor Overtemperature Factory Limit Fault | Cause: Calculations based on the motor thermistor indicate that the motor factory temperature limit has been exceeded. Remedy:
|
| FLT S07 – MTR OVERLOAD FL Motor Thermal Overload Factory Limit Fault | Cause: The motor thermal model has exceeded its factory set thermal capacity limit of 110%. Remedy:
|
| FLT S08 – MTR OVERLOAD UL Motor Thermal Overload User Limit Fault | Cause: The motor thermal model has exceeded the thermal capacity limit given by Motor Thermal Overload User Limit. Remedy:
|
| FLT S09 – MTR PHASE LOSS Motor Phase Loss | Cause: The motor has failed torque proving. Remedy:
|
| FLT S10 – INV OVERCURRENT Inverter Overcurrent Fault | Cause: Inverter current has exceeded the instantaneous current limit (determined by hardware). Remedy:
|
| FLT S11 – INV OVERTEMP FL Inverter Overtemperature Factory Limit Fault | Cause: The measured inverter temperature has exceeded the factory set temperature limit. Remedy:
|
| FLT S13 – INV OVERLOAD FL Inverter Thermal Overload Factory Limit Fault | Cause: The thermal model for the power transistors indicates that the temperature has exceeded the factory set thermal capacity rating of 110%. Remedy:
|
| FLT S14 – INV OVERLOAD UL Inverter Thermal Overload User Limit Fault | Cause: The thermal model for the power transistors indicates that the temperature has exceeded the limit given by Inverter Thermal Overload User Limit. Remedy:
|
| FLT S15 – CONV OVERCURRENT Converter Overcurrent Fault | Cause: The measured converter current has exceeded the factory set current limit. Remedy:
|
| FLT S16 – GROUND CURRENT Ground Current Factory Limit Fault | Cause: The sensing circuitry in the power stage has detected excessive ground current. Remedy:
|
| FLT S18 – CONV OVERTEMP FL Converter OverTemp Factory Limit Fault | Cause: The measured converter temperature has exceeded the factory set temperature limit. Remedy:
|
| FLT S20 – CONV OVERLOAD FL Converter Thermal Overload Factory Limit Fault | Cause: The converter thermal model indicates that the temperature has exceeded the factory set capacity rating of 110%. Remedy:
|
| FLT S21 – CONV OVERLOAD UL Converter Thermal Overload User Limit Fault | Cause: The converter thermal model indicates that the temperature has exceeded the limit given by Converter Thermal Overload User Limit. Remedy:
|
| FLT S23 – AC PHASE LOSS AC Single Phase Loss Fault | Cause: A single AC input phase was lost while the drive was enabled. Remedy:
|
| FLT S25 – PRECHARGE FAILURE Pre-charge Failure Fault | Cause: The pre-charge circuit monitoring algorithm detected that the DC bus did not reach a factory set voltage level after charging for a period of time. Remedy:
|
| FLT S29 – BUS REG OVERLOAD FL Bus Regulator Thermal Overload Factory Limit Fault | Cause: The shunt thermal model has exceeded its factory set thermal capacity limit. Remedy:
|
| FLT S30 – BUS REG OVERLOAD UL Bus Regulator Thermal Overload User Limit Fault | Cause: The shunt thermal model has exceeded the thermal capacity limit given by Bus Regulator Thermal Overload User Limit. Remedy:
|
| FLT S31 – BUS REG FAILURE Bus Regulator Failure | Cause: The shunt driver IC has detected that the shunt resistor is shorted. Remedy:
|
| FLT S33 – BUS UNDERVOLT FL Bus Undervoltage Factory Limit Fault | Cause: DC Bus voltage level is below the factory set limit as determined by the configured input voltage. Remedy:
|
| FLT S34 – BUS UNDERVOLT UL Bus Undervoltage User Limit Fault | Cause: DC Bus voltage level is below the user set limit as given by Bus Undervoltage User Limit. Remedy:
|
| FLT S35 – BUS OVERVOLT FL Bus Overvoltage Factory Limit Fault | Cause: DC Bus voltage level is above the factory set limit as determined by the configured input voltage. Remedy:
|
| FLT S39 – BUS POWER LEAK Bus Power Leakage Fault | Cause: Measured converter power exceeded estimated inverter output power by more than a factory limit. Remedy:
|
| FLT S45 – FDBK COMM FL Motor Feedback Data Loss Factory Limit Fault | Cause: The number of consecutive missed or corrupted serial data packets from the intelligent feedback device has exceeded a factory set limit. Remedy:
|
| FLT S47 – FDBK DEVICE FAILURE nn Feedback Device Failure | Cause: The feedback device has detected an internal error. The nn sub-code is defined as follows: 1: ACCELERATION OVERFLOW 4: TRACKING FILTER ERROR 5: VECTOR LENGTH ERROR 6: COUNTER ERROR 7: SYNCHRONIZATION ERROR 16: SINGLE TURN ERROR 17: MULTI TURN AMPLITUDE ERROR 18: MULTI TURN SYNC ERROR 19: MULTI TURN VECTOR LENGTH ERROR 35: STANDARD PARAMETER ERROR 36: INTERNAL COMMUNICATION ERROR1 37: INTERNAL COMMUNICATION ERROR2 38: INTERNAL SYSTEM ERROR 48: CRITICAL TEMPERATURE 49: CRITICAL LED CURRENT 50: CRITICAL SUPPLY VOLTAGE 51: CRITICAL SPEED 52: CRITICAL ACCELERATION 53: COUNTER OVERFLOW 54: INTERNAL MONITORING ERROR 66: INTERNAL RESOURCE ACCESS ERROR Remedy:
|
| FLT S49 – BRAKE SLIP FLT Brake Slip Exception | Cause: Motor slip has exceeded brake slip tolerance. Remedy:
|
| FLT S54 – POSN ERROR Excessive Position Error Fault | Cause: The position error of the position control loop has exceeded the value given by Position Error Tolerance for a time period given by Position Error Tolerance Time. Remedy:
|
| FLT S55 – VEL ERROR Excessive Velocity Error Fault | Cause: The velocity error of the velocity control loop has exceeded the value given by Velocity Error Tolerance for a time period given by Velocity Error Tolerance Time. Remedy:
|
| FLT S56 – OVERTORQUE LIMIT Overtorque Limit Fault | Cause: Motor torque has risen above user defined maximum torque level given by Overtorque Limit for a time period given by Overtorque Limit Time. Remedy:
|
| FLT S57 – UNDERTORQUE LIMIT Undertorque Limit Fault | Cause: Motor torque has dropped below user defined minimum torque level given by Undertorque Limit for a time period given by Undertorque Limit Time. Remedy:
|
| FLT M02 – MOTOR VOLTAGE Motor Voltage Mismatch Fault | Cause: The configured voltage of the drive is greater than the motor rated voltage. For example, a 400V-class drive with a 200V-class motor. Remedy:
|
| FLT M25 – COMMON BUS DC Common Bus Fault | Cause: AC power was detected by the drive while configured for shared DC operation. Remedy:
|
| FLT M26 – RUNTIME ERROR Runtime Error | Cause: The drive firmware encountered an unrecoverable runtime error. Remedy:
|
| FLT M28 – SAFETY COMM (2198-Hxxx-ERS2 drives only) Safety Module Communication Error | Cause: Communication with the safety hardware within the drive has failed. Remedy:
|
| INIT FLT M01 Smart Encoder Data Corruption | Cause: The data stored in the encoder has a checksum error. Remedy:
|
| INIT FLT M02 Motor Data Range Error | Cause: A motor data attribute stored in the encoder is out of range. Remedy:
|
| INIT FLT M03 Motor Feedback Communication Startup | Cause: Communication with the encoder could not be established. Remedy:
|
| INIT FLT M14 Safety Firmware | Cause: The loaded Safety firmware is not compatible with the drive firmware. Remedy:
|
| INIT FLT M20 Unknown Module | Cause: The product code of the power board is invalid. Remedy:
|
| INHIBIT S02 Motor Not Configured | Cause: The motor has not been properly configured for use. Remedy:
|
| INHIBIT S03 Feedback Not Configured | Cause: The feedback has not been properly configured for use. Remedy:
|
| INHIBIT M05 Start Inhibit – Safe Torque Off | Cause: The safety function has disabled the power structure. Remedy:
|
| NODE FLT 01 Control Connection Update Fault | Cause: Several consecutive updates from the controller have been lost. Remedy:
|
| NODE FLT 02 Processor Watchdog Fault | Cause: The processor on the power board or control board failed to update in a certain amount of time. (The nn sub-codes 00…06 are internal). Remedy:
|
| NODE FLT 03 – HARDWARE 00 Hardware Fault -PwrIF | Cause: Communication with the power board could not be established. Remedy:
|
| NODE FLT 03 – HARDWARE 01 Hardware Fault - Power Board | Cause: DSP chip on the power board failure. Remedy:
|
| NODE FLT 03 – HARDWARE 02 Hardware Fault - DSL | Cause: Communication with the encoder could not be established. Remedy:
|
| NODE FLT 03 – HARDWARE 03 DSL Internal Hardware Fault | Cause: A DSL hardware error internal to the drive was detected. Remedy:
|
| NODE FLT 03 – HARDWARE 04 Hardware Fault - Board Compatibility | Cause: The control and power boards are incompatible. Remedy:
|
| NODE FLT 05 Clock Skew Fault | Cause: The controller time and the drive's system time are not the same. Remedy:
|
| NODE FLT 06 Lost Controller Connection Fault | Cause: Communication with the controller has been lost. Remedy:
|
| NODE FLT 07 Clock Sync Fault | Cause: Drive's local clock has lost synchronization with controller's clock and was not able to resynchronize within allotted time. Remedy:
|
| NODE FLT 09 Duplicate IP Address Fault | Cause: Several consecutive updates from the controller have been lost. Remedy:
|
| NODE ALARM 01 Control Connection Update Alarm | Cause: Updates from the controller have been late. Remedy:
|
| NODE ALARM 03 Clock Jitter Alarm | Cause: The sync variance has exceeded the sync threshold while the device is running in sync mode. Remedy:
|
| NODE ALARM 04 Clock Skew Alarm | Cause: The controller time and the drive’s time are not the same. Remedy:
|
| NODE ALARM 05 Clock Sync Alarm | Cause: Drive's local clock has lost synchronization with controller's clock for a short time during synchronous operation. Remedy:
|
How to Clear & Reset Kinetix 5500 Servo Drive Faults
- Motion Axis Fault Reset (MAFR): In your Logix controller ladder logic program, trigger an execution pulse on the
MAFRinstruction targeted to the faulted CIP Motion axis. - Studio 5000 Motion Direct Commands (MDC): In Studio 5000 Logix Designer, open the Axis Properties for the drive, select Motion Direct Commands, choose Reset, and click Execute.
- CIP Safety & STO Reintegration: For drives with integrated safety (2198-Hxxx-ERS2) or hardwired STO (2198-Hxxx-ERS), verify that safety interlocks are healthy and safety run signals are reset in GuardLogix before commanding a Motion Servo On (
MSO). - Front Display Reset: On the drive faceplate, use the navigation pushbuttons next to the 4-character display to navigate to the fault menu and trigger a manual reset acknowledgment if permitted by controller ownership.
- Control & Mains Power Cycle: Remove main 3-phase AC input power and 24V DC auxiliary control power (BP connector). Wait at least 5 minutes until the shared DC bus discharge LED turns off and voltage drops below 50VDC before restoring power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous DC bus voltages remain present on the internal capacitors and external shared-bus bars (DC+ / DC-) after mains disconnect. Always measure with a calibrated digital multimeter across the DC bus terminals to verify voltage has dropped below 50VDC before handling motor power connections (U, V, W), feedback cables, or shared DC bus links.