Allen-Bradley PowerFlex 20P DC Drive Fault Codes & Diagnostic Guide
Complete fault code list, alarm diagnostics, root causes, and troubleshooting procedures for Rockwell Automation Allen-Bradley PowerFlex 20P series digital DC drives. Search or filter through the complete fault directory below.
Current / Power Range
7 – 1650 A DC (1.5 – 1400 HP)
Supply Voltage
230V / 460V / 575V / 690V AC
Control Modes
Speed & Torque DC Regulation
Operator Interface
20-HIM LCD Module / CCW
Complete Allen-Bradley PowerFlex 20P DC Fault Code Directory
Use the search box in the table below to quickly find your fault code (e.g., search F004, F016, F079, or Arm Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| F4 AC Undervoltage: There is an undervoltage on the power circuit (can only occur while the drive is active). | Cause:
Remedy:
|
| F5 Arm Overvoltage: There is an overvoltage on the armature circuit (125% of Par 175). | Cause:
Remedy:
|
| F2 Auxiliary Input: An auxiliary input interlock is open or a voltage (15...30V) is missing for digital input set to "Aux Fault". | Cause:
Remedy:
|
| F64 Drive Overload: The rated drive current was exceeded by 150% for 1 minute. | Cause:
Remedy:
|
| F132 Dsp Error: A non-resettable software error exists on the control board. | Cause:
Remedy:
|
| F100 EEPROM Error: Parameter values could not be saved or hardware config issue. | Cause:
Remedy:
|
| F92 Encoder Error: An error was detected with the Encoder signal. | Cause:
Remedy:
|
| F6 Fld Current Loss: The field current is too low (less than 50% of Par 468). | Cause:
Remedy:
|
| F95 Fwd End Limit: An end limit for the forward direction has been reached. | Cause:
Remedy:
|
| F97 Fwd Over Travel: A forward direction over travel signal has occurred. | Cause:
Remedy:
|
| F130 Hardware Fault: A non-resettable hardware error has occurred. | Cause:
Remedy:
|
| F8 Heatsink OvrTemp: The heatsink temperature is too high. | Cause:
Remedy:
|
| F131 Interrupt Error: A non-resettable software error in the main application. | Cause:
Remedy:
|
| F37 Inverting Fault: A digital input configured as "Invert Flt" has been removed. | Cause:
Remedy:
|
| F10 Main Contactor: Main or Dynamic Brake contactor failed to open/close in time. | Cause:
Remedy:
|
| F7 Motor Overload: The selected motor overload current level has been exceeded. | Cause:
Remedy:
|
| F16 Motor Over Temp: Motor exceeded temperature rating (via thermistor). | Cause:
Remedy:
|
| F0 No Fault / Info: Information only or HIM display issue. | Cause:
Remedy:
|
| F89 Open SCR: An open SCR fault condition has been detected. | Cause:
Remedy:
|
| F13 Overcurrent: An overcurrent occurred in the motor circuit. | Cause:
Remedy:
|
| F25 Overspeed: Speed feedback indicated speed > Par 585 [Overspeed Val]. | Cause:
Remedy:
|
| F48 Params Defaulted: User parameters reset to default values. | Cause:
Remedy:
|
| F71...75 Port 1...5 Adapter: The communication card has a fault. | Cause:
Remedy:
|
| F81...85 Port 1...5 DPI Loss: The DPI port stopped communicating. | Cause:
Remedy:
|
| F3 Power Failure: Fault in 24V control board supply or incoming voltage low. | Cause:
Remedy:
|
| F93 Resolver Error: An error was detected with the resolver signal. | Cause:
Remedy:
|
| F96 Rev End Limit: Reverse end limit reached. | Cause:
Remedy:
|
| F98 Rev Over Travel: Reverse direction over travel signal occurred. | Cause:
Remedy:
|
| F90 Shorted SCR: Shorted SCR fault condition detected. | Cause:
Remedy:
|
| F91 Spd Fdbk Loss: Speed feedback lost or inconsistent with armature voltage. | Cause:
Remedy:
|
| F20 SSC Error: Valid fiber packet not received within time period. | Cause:
Remedy:
|
| F62 STune Aborted: Speed regulator auto tuning stopped manually. | Cause:
Remedy:
|
| F59 STune CurLimit: Auto tuning current limit too high or speed zero levels high. | Cause:
Remedy:
|
| F60 STune FrictionLo: Friction value attained during tune is zero or too low. | Cause:
Remedy:
|
| F58 STune LoadHi: Loading torque too high at zero speed. | Cause:
Remedy:
|
| F56 STune Overspeed: Measured motor speed too high during tuning. | Cause:
Remedy:
|
| F57 STune Stalled: Drive stalled during speed regulator tuning. | Cause:
Remedy:
|
| F61 STune Timeout: Auto tuning did not complete within 15 minutes. | Cause:
Remedy:
|
| F70 Sustained Curr: Motor CEMF too high or current bridge change failed. | Cause:
Remedy:
|
| F94 TorqPrv Spd Band: Speed deviation exceeded level in Par 1105. | Cause:
Remedy:
|
| F99 Travel Lim Cflct: Travel limits are in conflict (Forward and Reverse active simultaneously). | Cause:
Remedy:
|
| Arm Overvoltage Type 1 | Cause: There is a possible overvoltage on the armature circuit or Par 175 [Rated Motor Volt] is set too low for the application. Remedy: See the “Arm Overvoltage” fault description in the manual (page 222) for more information. |
| Auxiliary Input Type 1 | Cause: An auxiliary input interlock is open or a voltage (15...30V) or reference signal is missing for the digital input set to 14 “Aux Fault”. Remedy: See the “Auxiliary Input” fault description in the manual (page 222) for more information. |
| BipolarCflct Type 2 | Cause: Par 1322 [Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or more of these digital input functions is configured: “Fwd/Reverse,” “Run Forward,” “Run Reverse,” “Jog Forward,” “Jog Reverse,” “Rev Dec Limit,” or “Rev End Limit.” Remedy: Check parameter configurations and ensure digital input functions match the Direction Mode setting. |
| BrakeSlipped Type 1 & 2 | Cause: The encoder movement has exceeded the level in Par 1110 [Brk Slip Count] after the brake was set.
Remedy: Cycle power to the drive to reset. |
| CntactrCflct Type 2 | Cause: Contactor input functions are in conflict.
Remedy: Program the parameter selections so that they match the relay output and/or digital input terminal block wiring correctly. |
| DigInCflctA Type 2 | Cause: Digital input functions are in conflict. Combinations of the following settings cause an alarm:
Remedy: Check digital input assignments and remove conflicting combinations. |
| DigInCflctB Type 2 | Cause: One of these digital input conflicts exists:
Remedy: Configure a Stop input, ensure Enable is configured, and resolve function conflicts. |
| DigInCflctC Type 2 | Cause: Multiple physical inputs have been configured to the same input function. Duplicate configurations are not allowed for:
Remedy: Remove duplicate input configurations. |
| FB Cfg Cflct Type 2 | Cause: Feedback configuration conflict has occurred:
Remedy: Correct the [Fdbk Device Type] or the associated source selection parameters (Pars 429, 430, 786, 1021, 1204, 1284). |
| FldCfg Cflct Type 2 | Cause: The selected operating mode of the field controller is in conflict with another setting, or a permanent magnet motor is incorrectly configured.
Remedy: Review parameters 469, 414, 478, 497, 498, and Digital Inx Sel for consistency. |
| Fld Current Loss Type 1 | Cause: The field current is too low. Remedy: See the “Fld Current Loss” fault description in the manual (page 222) for more information. |
| Motor Overload Type 1 | Cause: The selected motor overload current level has been exceeded. Remedy: See the “Motor Overload” fault description in the manual (page 223) for more information. |
| Motor Over Temp Type 1 | Cause: The motor has exceeded its temperature rating (as signaled by the thermistor connected to drive terminals 78 and 79). Remedy: See the “Motor Over Temp” fault description in the manual (page 223) for more information. |
| Ref Cflct Type 2 | Cause: Reference Conflict:
Remedy: Change the parameter selections so that unique sources are defined for the reference inputs. |
| Open SCR Type 1 | Cause: An open SCR condition has been detected (Par 213 bit 0 set and Par 216 set to “Alarm”). Remedy: See the "Open SCR" fault description in the manual (page 89) for more information. |
| Spd Fdbk Err Type 1 | Cause: With Par 478 [Spd Loss Flt Cfg] set to 1 “Alarm”, an error condition associated with the selected speed feedback device (analog tachometer, encoder, or resolver) was detected. Remedy: Check the speed feedback device connections and operation. |
| Spd Fdbk Loss Type 1 | Cause: Par 478 set to "Alarm". The speed feedback device indicates a value less than 5% of Max Feedback Spd, but the measured armature voltage is greater than the value of Par 455 [Spd FB Loss Lvl]. Remedy: See the “Spd Fdbk Loss” fault description in the manual (page 225) for more information. |
| Start At PowerUp Type 1 | Cause: Par 1344 [Start At Powerup] is enabled. Remedy: The drive can start at any time after power-up and the specified delay (Par 1345). Disable Par 1344 if this behavior is not desired. |
| Torq Prov Cflct Type 2 | Cause: Par 1100 [Torq Prove Cfg] is enabled, but a conflict exists:
Remedy: Check Par 1100, 1322, 414, 458, 457, 166, 58, 467, 498, 245, and 241 settings. Ensure relay outputs are not defined as "TP Brake Cmd" if not intended. |
| TP Encls Config Type 2 | Cause: The drive has been configured to enable Encoderless TorqProve, but an application conflict exists. Remedy: You must read and understand the “Attention” on page 309 relating to the use of TorqProve with no encoder before you can continue. |
How to Clear & Reset Allen-Bradley PowerFlex 20P DC Drive Faults
- Keypad Reset (20-HIM): Press the red Stop / Reset key on the 20-HIM digital keypad module. If running under network control, switch to local control or remove active start permissive signals before resetting.
- Digital Input Reset: If one of the discrete inputs on the control terminal block (configured via parameters 1391 – 1398 [Dig Inx Sel]) is mapped to “Clear Fault”, momentarily energize the input terminal.
- Software Diagnostic Reset (CCW / DriveExecutive): Connect via the DPI communication port or 1203-USB adapter, launch Connected Components Workbench or DriveExecutive, and click “Clear Faults” in the online diagnostic status window.
- Fieldbus Control Word: Write Bit 7 (Fault Clear) from `0` to `1` in the Logic Command word via your industrial fieldbus network (EtherNet/IP 20-COMM-E, ControlNet, DeviceNet, or PROFIBUS).
- Mains & Control Power Cycle: Disconnect the incoming 3-phase AC line supply and separate 115V/230V auxiliary control power (if installed). Wait for the HIM display and internal power LEDs to extinguish completely before restoring power.
⚠️ High-Voltage DC & AC Electrical Safety Warning:
PowerFlex 20P DC drives operate with dangerous AC line voltages and lethal DC potentials. Before servicing motor brushes, field coils, or internal power semiconductors, disconnect all incoming 3-phase AC lines and control power. Using a calibrated digital multimeter set to 1000V DC, verify zero electrical energy across armature terminals A1 / A2 and field terminals F+ / F- (or F1 / F2).